Frame Type
Fuse
[A]
Mains
cable
Cu [mm
2
]
Motor
cable
Cu [mm
2
]
Terminal cable size (min/max)
Main
terminal
[mm
2
]
Earth
terminal
[mm
2
]
Control
terminal
[mm
2
]
Relay
terminal
[mm
2
]
MI2 0001-0004 20 2*2.5+2.5 3*1.5+1.5 1.5-4 1.5-4 0.5-1.5 0.5-1.5
MI3 0005 32 2*6+6 3*1.5+1.5 1.5-4 1.5-4 0.5-1.5 0.5-1.5
Table 3.8: Cable and fuse sizes for Vacon 20, 115 V, 1~
Frame Type
Fuse
[A]
Mains
cable
Cu [mm
2
]
Motor
cable
Cu [mm
2
]
Terminal cable size (min/max)
Main
terminal
[mm
2
]
Earth
terminal
[mm
2
]
Control
terminal
[mm
2
]
Relay
terminal
[mm
2
]
MI1 0001-0003 10 2*1.5+1.5 3*1.5+1.5 1.5-4 1.5-4 0.5-1.5 0.5-1.5
MI2 0004-0007 20 2*2.5+2.5 3*1.5+1.5 1.5-4 1.5-4 0.5-1.5 0.5-1.5
MI3 0009 32 2*6+6 3*1.5+1.5 1.5-6 1.5-6 0.5-1.5 0.5-1.5
Table 3.9: Cable and fuse sizes for Vacon 20, 208 - 240 V, 1~
Frame Type
Fuse
[A]
Mains
cable
Cu [mm
2
]
Motor
cable
Cu [mm
2
]
Terminal cable size (min/max)
Main
terminal
[mm
2
]
Earth
terminal
[mm
2
]
Control
terminal
[mm
2
]
Relay
terminal
[mm
2
]
MI1 0001-0003 6 3*1.5+1.5 3*1.5+1.5 1.5-4 1.5-4 0.5-1.5 0.5-1.5
MI2 0004-0007 10 3*1.5+1.5 3*1.5+1.5 1.5-4 1.5-4 0.5-1.5 0.5-1.5
MI3 0011 20 3*2.5+2.5 3*2.5+2.5 1.5-6 1.5-6 0.5-1.5 0.5-1.5
MI4 0012-0025
20
25
40
3*6+6 3*6+6 1-10Cu 1-10 0.5-1.5 0.5-1.5
MI5 0031-0038 40 3*10+10 3*10+10
2.5-50
Cu / Al
2.5-35 0.5-1.5 0.5-1.5
Table 3.10: Cable and fuse sizes for Vacon 20, 208 - 240 V, 3~