User manual
72 • vacon parameters
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
8
P3.4
Preset speed 0 P3.1 P3.2 Hz 5,00 180
Preset speed 0 is used
as frequency reference
when P3.3 = 1
P3.5
Preset speed 1 P3.1 P3.2 Hz 10,00 105
Activated by digital
inputs
P3.6
Preset speed 2 P3.1 P3.2 Hz 15,00 106
Activated by digital
inputs
P3.7
Preset speed 3 P3.1 P3.2 Hz 20,00 126
Activated by digital
inputs
Acceleration
time 1
0,1 3000,0 s 3,0 103
Acceleration time from
0 Hz to maximum fre-
quency.
Deceleration
time 1
0,1 3000,0 s 3,0 104
Deceleration time from
maximum frequency to
0 Hz.
P6.1 AI1 Signal range 0 1 0 379
0 = 0 - 100%
1 = 20% - 100%
20% is the same as 2 V
minimum signal level.
P6.5 AI2 Signal range 0 1 0 390
0 = 0 - 100%
1 = 20% - 100%
20% is the same as 2 V
or 4 mA minimum signal
level.
Automatic reset 0 1 0 731
0 = Disable
1 = Enable
P17.2
Parameter
conceal
0 1 1 115
0 = All parameters visi-
ble
1 = Only quick setup
parameter group visible
Code Parameter Min Max Unit Default ID Note
Table 8.1: Quick setup parameters
i
i
i
i
P4.2
P4.3
P14.1
i