74 vacon parameters
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
8
Brake Chopper 0 2 0 504
0 = Disabled
1 = Enabled: Always
2 = Run state
Brake chopper
level
0 911 V varies 1267
Brake chopper control
activation level in volt.
For 240V Supply:
240*1.35*1.18 = 382V
For 400V Supply:
400*1.35*1.18 = 638V
Please note that when
brake chopper is used the
overvoltage controller can
be switched off or the
overvoltage reference level
can be set above the brake
chopper level.
Motor
identification
02 0 631
0 = Not active
1 = Standstill identification
(need run command within
20 s to activate)
2 = Identification with run
(need run command within
20 s to activate. Only availa-
ble in power SW V026
included in FW01070V010
or later version)
Rs voltage drop 0,00
100,0
0
%0,00662
Voltage drop over motor
windings as % of U
nmot
at
nominal current.
Overvoltage
controller
02 1 607
0 = Disabled
1 = Enabled, Standard
mode
2 = Enabled, Shock load
mode
Undervoltage
controller
01 1 608
0 = Disable
1 = Enable
Sine filter 0 1 0 522
0 = Not in use
1 = In use
Code Parameter Min Max Unit Default ID Note
Table 8.2: Motor settings
P1.17
i
P1.18
P1.19
i
P1.20
P1.21
i
P1.22
i
P1.23