8.7 Analogue inputs (Control panel: Menu PAR -> P6)
8.8 Pulse train / Encoder (Control panel: Menu PAR -> P7)
Code Parameter Min Max Unit Default ID Note
P6.1 AI1 Signal range 0 1 0 379
0 = 0 - 100% (0 - 10 V)
1 = 20% - 100% (2 - 10 V)
P6.2 AI1 Custom min
-100,00
100,00 % 0,00 380 0,00 = no min scaling
P6.3 AI1 Custom max
-100,00
300,00 % 100,00 381 100,00 = no max scaling
P6.4 AI1 filter time 0,0 10,0 s 0,1 378 0 = no filtering
P6.5 AI2 signal range 0 1 0 390 As parameter P6.1
P6.6 AI2 Custom min
-100,00
100,00 % 0,00 391 As parameter P6.2
P6.7
AI2 Custom max
-100,00
300,00 % 100,00 392 As parameter P6.3
P6.8
AI2 filter time 0,0 10,0 s 0,1 389 As parameter P6.4
P6.9 AIE1 Signal range 0 1 0 143
As parameter P6.1, hid-
den until an option board
is connected
P6.10 AIE1 Custom Min
-100,00
100,00
% 0,00 144
As parameter P6.2, hid-
den until an option board
is connected
P6.11 AIE1 Custom Max
-100,00 300,00
% 100,00 145
As parameter P6.3, hid-
den until an option board
is connected
P6.12 AIE1 Filter time 0,0 10,0 s 0,1 142
As parameter P6.4, hid-
den until an option board
is connected
Table 8.7: Analogue inputs
Code Parameter Min Max Unit Default ID Note
P7.1
Min pulse fre-
quency
0 10000 Hz 0 1229
Pulse frequency to be
interpreted as a 0% signal.
P7.2
Max pulse fre-
quency
0,0 10000 Hz 10000 1230
Pulse frequency to be
interpreted as a 100%
signal.
P7.3
Freq. ref. at min
pulse freq.
0,00
P3.2 Hz 0,00 1231
Frequency correspond-
ing to 0% if used as fre-
quency reference.
P7.4
Freq. ref. at max
pulse freq.
0,00
P3.2 Hz
50,00 /
60,00
1232
Frequency correspond-
ing to 100% if used as
frequency reference.
Table 8.8: Pulse train/Encoder