parameters vacon 89
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
8
UL:Time limit
1,0
300,0 s 20,0 716
This is the maximum
time allowed for an
underload state to exist
P13.17
Analog Input low
fault delay
0,0
10,0 s 0,5 1430
Delay time for analog
input low fault
External fault
0
3 2 701 Same as parameter 13.3
P13.19 Fieldbus fault 0 4 3 733 As parameter 13.1
P13.20
Preset alarm fre-
quency
P3.1 P3.2 Hz 25,00 183
Frequency used when
fault response is Alarm +
preset Frequency.
P13.21
Parameters edit
lock
0 1 0 819
0 = Edit enabled
1 = Edit disabled
P13.22 Thermistor Fault 0 3 2 732
0 = No action
1 = Alarm
2 = Fault: Stop function
3 = Fault: Coast
Hidden until an option
board is connected.
P13.23
FWD/REV con-
flict supervision
0 3 1 1463 Same as P13.3
P13.24
Temperature
fault
0 3 0 740
As parameter P13.3, hid-
den until an OPTBH
board is connected
P13.25
Temperature
fault input
1 7 1 739
Binary-coded selection of
signals to use for alarm
and fault triggering
B0 = Temperature input 1
B1 = Temperature input 2
B2 = Temperature input 3
NOTE! Hidden until an
OPTBH board is connected
P13.26
Temperature
fault mode
0 2 2 743
0 = Not used
1 = Low limit
2 = High limit
P13.27
Temperature
fault limit
-50,0/
223,2
200,0/
473,2
100,0 742
Temperature fault
threshold, hidden until
an OPTBH board is con-
nected
Code Parameter Min Max Unit Default ID Note
Table 8.14: Protections