User manual
90 • vacon parameters
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
8
NOTE!
* These parameters are only available in power SW FWP00001V026 included in
FW01070V010 or later versiond.
NOTE! These parameters are shown, when P17.2 = 0.
8.15 Fault autoreset parameters (Control panel: Menu PAR -> P14)
NOTE! These parameters are shown, when P17.2 = 0.
Input phase fault* 0 3 3 730
As parameter P13.3
Motor tempera-
ture
memory mode*
0 2 2 15521
0 =
disabled
1 =
constant mode
2 =
last value mode
Code Parameter Min Max Unit Default ID Note
Automatic Reset 0 1 0 731
0 = Disabled
1 = Enable
Wait time 0,10 10,00 s 0,50 717 Waiting time after fault
Trial time 0,00 60,00 s 30,00 718 Maximum time for trials
Trials number 1 10 3 759 Maximum trials
Restart Function 0 2 2 719
0 = Ramping
1 = Flying
2 = From Start Function
Table 8.15: Fault autoreset parameters
Code Parameter Min Max Unit Default ID Note
Table 8.14: Protections
P13.28
i
P13.29
i
P14.1
i
P14.2
P14.3
i
P14.4
P14.5