Input/Output
Contact FIC 1984-1460-000x.......................................
1984-1304-000x...................................................
Contact FIC Specifications
Item
Specification
Power:
Voltage
Current
22--34 VDC
90 mA at 30 V typical.
Switching c urrent 10 mA typical,
8 mA m inimum
Contact FIC LEDs
LEDs
Meaning
DS5--DS10
I/O 1--6: Indicates the logic state of the moduleā€˜s input or output. With
a normally open input or output, the module is on if the LED is on. With
a special order normally-closed output module, contact is made with no
power applied. The LED is on with an open contact on the module.
DS3
30V Fuse Blown: Replace power fuse F1 on the Contact Field Interface
Card.
DS4
TX Enable: The signal which enables the transmit signal from the Field
Interface Card to the Contact Processor is active.
DS2
Card Fault: A Fault is detected on the contact Field Interface card, or
communications with the contact processor have ceased. Discrete
outputs will go to the condition called for by the position of jumper HD1
(hold or off).
DS1
Card Good: No faults are detected on the Contact Field Interface card
and communication with the Contact Processor is active.