Specifications
SQ: 7-31
RS3: Service Quick Reference Guide
Input/Output
Analog Input FIC: Non-Isolated 1984-1463-0001....................
1984-1394-000x...................................................
Non-Isolated Analog Input FIC LEDs
LEDs
Meaning
--
30V Fuse Blown: The 30 VDC power fuse to the card is blown. Note
that this LED does not indicate whether field transmitter power and
input current fuses are operational.
DS1 +12V Status: Power is present and the regulator is operational.
Non-Isolated Analog Input FIC Test Points
Test Points
Meaning
Brown Ground return.
Yellow 1 to 5 V analog signal to controller.
Non-Isolated Analog Input FIC Jumper Positions
Jumper
Position Purpose
HD1 1--2: System supplies power to
transmitter output device.
2--3: Transmitter or output device
supplies its own power.
Specifies FICs power setup.
Non-Isolated Analog Input FIC Fuses
Fuse
FRSI
Part No.
Bussman
Part No.
Littelfuse
Part No.
Characteristics
F1
F2
F3
G09140--0010 AGC 1/4 312.250 1//4 A 250 V Quick Acting