Specifications
SQ: 7-33
RS3: Service Quick Reference Guide
Input/Output
Analog Input FIC: Isolated 1984--1325--0001........................
Isolated Analog Input FIC LEDs
LEDs
Meaning
DS4
Input Signal: Indicates that the field input is present. The LED glows
brighter as the field input increases. With no input, the LED is off.
DS3
30V Fuse Blown: The 30 VDC power fuse to the card is blown. Note
that this LED does not indicate whether field transmitter power and
input current fuses are operational.
DS2
+12V Non-Isolated Status: The non -isolated +12 V regulator is
operational.
DS1 +12V ISO Status: The isolated +12 V regulator is operational.
Isolated Analog Input FIC Test Points
Test Point
Meaning
Yellow 1 to 5 V analog signal to controller.
Brown Ground return.
Isolated Analog Output FIC Jumper Positions
Jumper
Position Purpose
HD1 1--2 System supplies power to transmitter or output device.
2--3 Transmitter or output device supplies it own power.
Isolated Analog Output FIC Fuses
Fuse
FRSI P/N Bussman P/N Littelfuse P/N Characteristics
F1
F2
G09140--0010 AGC 1/4 312.250
1/4 A 250 V Quick
Acting
F3 G09140--0016 AGC 1/2 312.500
1/2 A 250 V Quick
Acting