Specifications
SQ: 7-39
RS3: Service Quick Reference Guide
Input/Output
Remote Communications Termination Panel II 1984--4205--0001......
Remote Communications Termination Panel I 1984--2552--0001......
Remote Communications Termination Panel Parts Replacement
Part No
Replaces Characteristics
1984--4409--0001
(Kit)
1984--2552--000x
The K it replaces a Remote
Communications Termination Panel I.
The kit contains two Remote
Communications Termination Panel II units
and a DIN rail for mounting them.
Remote Communications Termination Panel II Jumpers
Jumper
Position Effect
HD1
REMOTE I/O
(1--2)
Used when the panel is at the remote end of the
communication line; at the c ard c age or FlexTerm.
CONT FILE
(2--3)
Used when the panel is at the ControlFile (source)
end of the c ommunication line.
HD4A
HD4B
NORMAL
(1--2)
Normal operation. One cable is used from the
ControlFile to the panel. The panel is connected
to one Controller Processor.
REDUNDANT
(2--3)
Redundant operation. Two cables are used
between the ControlFile and the panel. The panel
is connected to two Controller Processors.