Specifications

SQ: 7-47
RS3: Service Quick Reference Guide
Input/Output
Multi-FIM Discrete Termination Panel 1984--4282--0001..............
Multi-FIM Discrete Termination Panel Jumpers
Jumper
Value Effect
HD1,2,3 AON
FIM address A (factory setting)
NOTE: Only one jumper is allowed in positions A--D
BON FIM address B
CON FIM address C
DON FIM address D
EOFF Not used
FON Factory setting, do not move
HD4--8 1--2 Normal individual FIM operation
2--3 Redundant operation of FIMs A and B
HD9, 10, 11
1--8 OFF
2--7 ON
3--6 ON
4--5 ON
Normal loop operation
1--8 ON
2--7 OFF
3--6 OFF
4--5 OFF
Used with Intrinsically Safe barriers
CAUTION
Remove power from the panel before moving jumpers on
HD9, 10, or 11. The FIM may be damaged if 1--8 is ON
when any of the other positions are ON.
HD12
OFF
(No
jumpers)
Communication Ports A and B are independent
(normal operation of FIMs A and B)
1--12 ON
3--10 ON
5--6 ON
Communication Ports A and B are connected
(for online replacement operation of FIMs A and B)