Specifications

SQ: 7-48
RS3: Service Quick Reference Guide
Input/Output
Isolated Discrete Termination Panel
A 1984--4121--0001................................................
B 1984--4124--0001................................................
NOTE: You must configure an I/O Block at FIM I/O address 1 to set the
switch voltage for the entire FIM. Set to 1.7 volts for reliable operation.
WARNING
The solid state relays may be hot enough to cause
burns.
Solid State Relays
Part Number
C12243--
Model Function
Output
Contact*
Voltage Color
0005 IAC5A AC Input None 180--280 VAC/DC** Yellow
0006 IDC5 DC Input None 10--32 VDC White
0007
IDC5--B
IDC5--F
DC Input None 4--16 VDC White
0008 IAC5 AC Input None 90--140 VAC/DC** Yellow
0009 ODC5
DC
Output
N.O. 5--60 VDC Red
0010 ODC5A
DC
Output
N.O. 5--200 VDC** Red
0011 OAC5A5
AC
Output
N.C. 24--280 VAC** Black
0012 OAC5
AC
Output
N.O. 12--140 VAC** Black
0013
OAC5--A
OAC5--1
AC
Output
N.O. 24--280 VAC** Black
0014
IDC5G
IDC5N
DC Input None 35--60 VAC/DC White
0015
ODC5RM
ORR5--1
Dry
Contact
Relay
N.O.
100 VDC
130 VAC
(Max switching
current .5 A,
10 VA contact rating)**
* All output modules, except OAC5A5, have normally open (N.O.) outputs. The output
contact is open when the block output is FALSE.
** CAUTION
Hazardous voltages may be present on field wiring.
Lock out and tag hazardous voltage circuits prior to
servicing.