Input/Output
Isolated Discrete Termination Panel A Jumpers
Jumper
Value Effect
HD1
(Panels “A” & “B”)
A Card cage A (factory setting)
B Card cage B
C Card cage C
D Card cage D
E Not used
F Factory setting, do not move
HD2
(Panel “A” only)
Both Jumpers ON
or
both jumpers at
NORM
or both wires intact
Normal single FIM operation
with online replacement capability
Both Jumpers OFF
or
both jumpers at
FIM REDUND
or
both wires cut
Redundant FIM operation
Isolated Discrete Termination Panel Fuses
Fuse
FRSI
Part No.
Littelfuse
Part No.
Wickman
Series
Characteristics
F1 to
F32
G53394--3150--0005 216 3.15
19 194
3.15 A
3.15 A 250 V (IEC)
Quick action
5x20 mm Ceramic
CAUTION
Hazardous voltages may be present. Lock out and tag
hazardous voltage circuits prior to servicing.