Specifications

SQ: 7-52
RS3: Service Quick Reference Guide
Input/Output
MAIO16 Termination Panel
(Field wires land on panel) 10P54770001...........................
(Field wires on panel or on marshaling panel) 10P54770002.. .....
MAIO16 is EMC compliant.
NOTE: All input points must be constrained to operate within the
common mode range of +29 to --2 VDC. This is automatic when all inputs
are system powered. The ground levels must remain within ± 2 Volts of
each other or erroneous results will be reported. The ground reference is
available on TB17.
Parts Replacement for the MAIO16 Termination Panel
Part No.
Replaces Characteristics
1984--4383--0001 Replaces all cases.
10P54770001
10P54770002
1984--4383--0002
Only if marshaling cable is not used.
10P54770002
10P54770001
1984--4383--0001
1984--4383--0002
Replaces all cases.
MAIO16 Termination Panel Jumpers
Jumper
Value Effect
HD1--HD16 Full left
Self-Powered Input Point with external ground
reference or Output Point
Centered System-Powered Input Point
Full right
Self-Powered Input Point with ground reference
at the Termination Panel
HD17 Aat1--2 Cage address A (Factory setting)
Bat1--2 Cage address B
Cat1--2 Cage address C
Dat1--2 Cage address D