Specifications

SQ: 7-56
RS3: Service Quick Reference Guide
Input/Output
MAI32 Termination Panel
(Field wires land on panel) 10P53490001...........................
(Field wires on panel or on marshaling panel) 10P53490002.........
The panel supports 32 analog input points u sing two termination panel
addresses and two input blocks. The first address supports the Left Group
of points (L1--L16), the second address supports the Right Group of points
(R1--R16). An Analog Input Block (AIB) or a Smart Transmitter Input Block
(SIB) must be configured for each address. HART variables can be
addressed by configuring a VIB.
The Field I/O Status Screen (previously the FIC Status Screen) shows the
type of device connected to each controller. The MAI32 FIM will have two
entries, one for each cage address used. The type code is “MAI32-x”
where the “x” shows the card cage of the OTHER set of 16 points. Thus if
the panel is addressed as A and C, the first entry will show “MAI32-C” and
the s econd will show “MAI32-A”.
Multipoint Analog I/O Termination Panel Parts Replacement
Part No
Replaces Comments
10P53490001 10P53490002 Only if marshaling cable is not used.
10P53490002 10P53490001 Valid for all cases.
MAI32 Termination Panel Jumpers
Jumper
Position Effect
HDL01--HDL16
HDR01--HDR16
Full left System-powered input point
Point Type Full right Self-powered input point
HD33
One jumper
A--C at 1--2
Cage address for Left Group of points
L01--L16 (A is recommended)
ADDRESS
One jumper
B--D at 1--2
Cage address for Right Group of points
R01--R16 (B is recommended)
Pat1--2 Required for correct parity
(continued on next page)