Specifications

SQ: 7-63
RS3: Service Quick Reference Guide
Input/Output
MAI32 Input FIM (EMC Approved) 10P53190004.....................
The FIM supports 32 analog input points using two termination panel
addresses and two input blocks. The first address supports the Left Group
of points (L1--L16), the second address supports the Right Group of points
(R1--R16). An Analog Input Block (AIB) or a Smart Transmitter Input Block
(SIB) must be configured for each address. HART variables can be
addressed by configuring a VIB.
The Field I/O Status Screen (previously the FIC Status Screen) shows the
type of device connected to each controller. The MAI32 FIM will have two
entries, one for each cage address used. The type code is “MAI32-x”
where the “x” shows the card cage of the OTHER set of 16 points. Thus if
the panel is addressed as A and C, the first entry will show “MAI32-C” and
the s econd will show “MAI32-A”.
MAI32 Input FIM LEDs
LED
Meaning
On: FIM Good
Flashing: FIM Inactive
(Green)
ON steady when the FIM is in normal operation.
Flashing when the FIM is disconnected from the field.
FIM Failure
(Red)
ON when FIM considers itself failed.
Flashing when FIM is not communicating with the
Controller.
Port A Active
(Yellow)
Flashes when communication Port A is active.
Port B Active
(Yellow)
For factory use only.
Status 1
(Yellow)
Flashes steadily while the FIM operates.
Status 2
(Yellow)
Flashes a diagnostic code when the FIM is disabled and
the red LED i s ON.