Specifications
SQ: 1-48
RS3: Service Quick Reference Guide
Troubleshooting
FIC/FIM Status Bits
Status for:
Status Bits Bit Description
Any
NON-
BOOT
Indicates that the FIC/FIM program needs to
be loaded.
Analog FIC
Bits:
1xxx xxxx 7
Lost calibration: Set to 1 if any A/D or D/A
calibration constants become questionable.
x1xx xxxx 6
A/D converter failure. Set to 1 if any A/D
converter does not complete a conversion
within 45 milliseconds.
xx1x xxxx 5
Smart Transmitter message available. Set
to 1 when a message is available.
xxx1 xxxx 4
Redundancy Jumper. Set to 1 for 1:1
redundancy. Set to 0 for other redundancy
(including none).
xxxx 1xxx 3
Output Bypass Unit status. Set to 1 when
the Output Bypass Unit is active.
xxxx x1xx 2
Hold/Zero jumper setting. Set to 1 to hold
output value i f a problem occurs.
xxxx xx1x 1
Normal/Inverse acting v alve jumper setting.
Set to 1 for inverse acting valves.
xxxx xxx1 0
Background diagnostics failure. Set to 1 if
any background diagnostic test (except
calibration constants) fails.
Analog FIM
Bits:
1xxx xxxx 7
Indicates the health of the other FIM. Set to
1 i f the other FIM is “sick” or missing.
x1xx xxxx 6
Set to 1 if this FIM is disconnected from the
field.
xx1x xxxx 5
Indicates the health of this FIM. Set to 1 if
this FIM is “sick”.
xxx1 xxxx 4
Input Data Validity; Set to 0 if the data is
good.
Set to 1 if the data is
invalid.
Output Data Validity: This bit is not used
for outputs.
(continued on next page)