Specifications

SQ: 3-5
RS3: Service Quick Reference Guide
Power
AC/DC Power Supply
(With Battery Backup) 10P5658000x...............................
1984-2298-000x...................................................
1984-0298-000x...................................................
OI Remote Power Supply 1984-1046-000x..........................
AC/DC Power Supply (With Battery Backup) Parts Replacement
Part No.
Replaces Comment
10P5658000x
1984--0298--000x
1984--2298--000x
The 10P5658000x supply i s CE-compliant
1984--2298--000x 1984--0298--000x Supplies are fully interchangeable
1984--0298--000x 1984--2298--000x Supplies are fully interchangeable
1984--2298--000x
or
1984--0298--000x
1984--0390--000x
Either supply may replace a --0390 AC/DC
Power Supply (Without Battery Backup) but
the BATT switch must be turned OFF.
NOTE: The PS FAULT alarm jumper
(HD1) must be s et to 2--3 since the --0390
contacts are Normally Closed (N.C.).
Power Supply (With Battery Backup) Indicators and Controls
Item
Function
BATT
ON/OF Toggle
Switch
Removes the battery backup c ircuit from the system when in OFF
position.
BATT TEST
Pushbutton
The B attery Test Pushbutton is used to manually enable the 16 amp,
5 second battery test. If battery voltage falls below 20 V during the
test, the BATT FAULT LED lights and the battery alarm activates.
NOTE: The battery cannot be tested until the system has been
running for at least five minutes or until five minutes after the last
battery test.
AC IN
Indicator (Orange)
Indicates that AC input is present.
(continued on next page)