Specifications
© Systeme Lauer GmbH & Co KG • Kelterstr.59 • 72669 Unterensingen • Tel. (07022) 96 60-0 • Fax (07022) 96 60-103
D-4
D Buep 19e-Direct driver
Communication ERROR When communicating with each other the PCS operates as master (AST)
and the PLC as slave (PST). Thus, it is the PCS´s task to set up the
communication and to perform monitoring. Thereby, 3 criteria must be
monitored: is communication active, is communication processing in the
PLC active, and does the PLC in dicate faults. Data are transferred to/
read from the PLC via the BUEP19E protocol. The timeout times for the
protocol are fixed (2.4s max.) which allows no statement about data
processing. Therefore, the processing timeout is set using the PROJEKT/
DRIVER PARAMETER menu in PCSPRO.
In case of an error, an error message is displayed on the PCS and the
ERROR LED flashes. The PCS tries to set up communication again in
the background. The error message is erased if this has been successful.
Error message (whereby the fault text on the bottom line is described
below):
========== COMMUNICATION ERROR ==========
FAULT TEXT
• TIMEOUT COMMUNICATION
This error message is output if the protocol timeout time of 2.4
seconds expires.
• TIMEOUT PLC
This display is shown in case the task packet is not processed by
the PLC. This is the case if the program will not execute PCS_ KOMM,
or the restart input is not set following a communication loss. The
Timeout time for the order processing is settable via the timeout
parameter in the range of 2 s to 9.9 s. This fault appears only during
synchronous operation.
• PLC ERROR RECEIVED
The PLC indicates via the BUEP19E protocol if a fault has appeared.
This can happen if the addressed data block is too small or not present
or an inadmissible access occurs. Therefore, examine the settings
of the driver variables and the definitions in the PLC (e.g. symbol
file).
• TOO MANY REPETITIONS
The faulty position is repeated if a fault appears in the communication.
The communication is interrupted and the following error message
is output after 3 unsuccessful repetitions. In this case the PCS/PLC
connection has been routed through a noisy environment, the cable
is too long for the selected baud rate, or earthing is insufficient.
• PLC IN STOP
This error message is output if the status of the PLC has been check
and the CPU was not in „RUN“ mode.
• WRONG BLOCK NUMBER
The block address of the CPU (set via CPU slot) to be addressed is
checked by the protocol. This error message is output if the corres-
ponding CPU is not present.