Specifications

9261-7974 Issue 06
ESFIRECODER - Emergency Services Firecoder
Page 13
www.multitone.com
Sh{h} - Set Command
This command, when followed by one or more hex characters, will set one or more outputs, for
example "S046" will set outputs 0,4 and 6 leaving the others unchanged.
Rh{h} - Reset Command
This command, when followed by one or more hex characters, will reset one or more outputs,
for example "R17" will reset outputs 1 and 7 leaving the others unchanged.
Ohhhh - Output Command
This command sets all outputs to the states specified in the four following hex characters. The
O, S and R commands will reply with the current output states as "ohhhh". Outputs 0..5
correspond to the front panel LED's as follows:
Channel LED
0 User 1
1 User 2
2 User 3
3 Fault
4 Flash Red (Mains Fail)
5 Flash Green (Low Battery)
Ttext - Text for Display
This command allows text to be sent to the display, so it is only valid when the unit is in front
panel mode. Up to 250 characters may be sent in a single line. The following special display
control commands are available:
Character Function
\ f Clear Display
\ r Move cursor to start of line 1
\ n Move cursor to start of line 2
\ t Clear to end of line
\ \ Display a single \ character
\ u Display user defined symbol
\ d Display 'delete' symbol