Specifications
9261-7974 Issue 06
ESFIRECODER - Emergency Services Firecoder
Page 26
www.multitone.com
Notes The page command will use an Alerter_1 agent type if no Alerter_2 type is found.
The Agent Manager for a Peripheral or Console Agent will default to sending ACTIVATE
and DEACTIVATE commands to itself unless a destination for the message is specified.
PRINT DFLT_Printer
DISPLAY DFLT_Mobilise
PAGE DFLT_Alerter_2 or DFLT_Alerter_1
SEND DFLT_Paging
PLAY DFLT_Sound
ACTIVATE DFLT_Peripheral
DEACTIVATE DFLT_Peripheral
EMAIL DFLT_Email
6.13 Agent Events: Peripheral/Console /Remote Console/Button Box Agents
This agent type will send the following events to the agent manager:
chan:On Channel On
chan:Off Channel Off
chan:Wait Wait before turnoff
chan:Regen Regenerated message sent
chan:Moni Channel monitored OK
chan:Fail Monitoring failed
chan:Mobi Channel mobilised
chan:Actv Channel activated
chan:Deac Channel deactivated
Command:n UFI Front Panel command
Command:Fx Button Box Fire (x = A, B, C, AB, AC, BC, ABC)
Command:Tx Button Box Test (x = A, B, C, AB, AC, BC, ABC)
Command:FT Button Box Engineering Command
Tones:xxxx Tone Sequence xxxx received from LPI
chan is the configured name of the channel, but with any spaces changed to underscores.
A chan:Wait event is sent 60 seconds before an output turns off. However, if the configured time for
the output is less than 60 seconds, the event is sent when half the time has elapsed.