Discover Manual

5
discoverbattery.com
3. Design Features and Components
3.1 Integrated Battery Management System (BMS)
Monitors
Cell module voltages
Battery voltage
Battery current
Battery temperature
Battery state of charge (SOC)
Module Balancing
Performs balancing of cell modules
Protection and Operating Limits
BMS will open its internal relay when maximum operating limits are exceeded
When the condition returns to its nominal operating range, most protections will be released and reset after 120s
Communication Ports
Isolated USB and CAN communication
Data Logging
Logged data is accessed using AES Dashboard software via the USB port (Win64 supported)
3.2 Internal Battery Fuse
The internal battery fuse provides back-up over-current protection. External fusing should be sized correctly to protect the circuit
and circuit cabling.
A blown fuse requires replacement by a qualied installer - contact your Discover installer.
3.3 Protections
The BMS will open the internal relay to protect against operation outside of maximum specications. During a protection the key
LED will ash at 1 Hz. Most protections will be automatically recovered once the condition is cleared with the exception of the
low voltage protection.
Protection Auto Recoverable Description
Over Voltage Yes
Protection is triggered when any cell module voltage exceeds the
threshold value for 5 seconds. After the voltage falls below the
trigger for 120 seconds the protection is cleared.
Under Voltage No
Protection is triggered when any cell module voltage falls below the
threshold value for 5 seconds. The battery will turn itself off after 120s.
High Current Yes
Protection is triggered when current exceeds the threshold value. The
protection will be cleared after 120 seconds.
High Temperature Yes
Protection is triggered when the battery temperature exceeds the
threshold value for 5 seconds. After the temperature falls below the
recovery temperature the protection is cleared.
Low Temperature Yes
Protection is triggered when the battery temperature falls below the
threshold value for 5 seconds. After the temperature raises above the
recovery temperature the protection is cleared.
4. Handling
WARNING!
Read Safety Section before handling the battery.
Battery should be set to OFF
Battery cables should be disconnected
Battery terminals should be protected
Battery handle should be used to lift battery
Battery should be handled by two people or mechanical lift equipment
Do not lift or carry the battery during usage or operation
Do not lift the battery with the battery cables