Discover Manual

9
discoverbattery.com
CAUTION!
Always make sure the charge curve parameters of the charging device
are set to meet the charging requirements of the battery; never charge a
visibly damaged battery; never charge a frozen battery.
1. Connect the Power Conversion device’s charger leads to the battery.
2. Ensure the charger and battery side connections are tight.
3. Set the charger to ON
4. Set the battery to ON
CAUTION!
NOT ALL CHARGERS ARE CAPABLE OF CHARGING LITHIUM BATTERIES
CONFIRM that your chosen charger is incapable of producing transient
spikes that exceed the published terminal voltage limits for the battery.
Spikes are fast, short duration electrical transients in voltage (voltage spikes), current (current spikes), or transferred energy
(energy spikes) in an electrical circuit. Voltage spikes usually happen when the AC/DC adapter is plugged in, or charge current is
cut off quickly. Multi voltage chargers are constructed using transformers that may be capable of producing spikes that exceed
the maximum ratings of the Discover AES Battery. You must ensure that the charger being supplied:
Meets the recommended charge curve
Incapable of exceeding Discovers maximum terminal voltages
7.3 Open Loop Charge Curve
1. Charge at constant current to 3.4 V per cell module (Bulk).
2. Maintain constant voltage 3.4 V per cell module (Absorption).
3. Terminate when charge current drops below 2A.
4. Optional Float at 3.35V per cell module (Float).
Absorption
Charge Current % of Bulk Charge C-Rate [%]
Voltage - U Current - I
Bulk
Cell Voltage [V]
2.8
20%
40%
60%
80%
100%
3
3.2
3.4
3.6
I1Max
I1Rec
U1