Install Instructions

Doc # INT-100000-002
Part No. 191452 Rev. 5
INSTALL INSTRUCTIONS
DTK-CMXPLUS Series
INSTALLATION
Drawn By: R. Mitchell 11-6-17
Approved By: R. Mitchell 11-6-17
BREAKER PANEL
GROUND BUS
GREEN WIRE
BLACK WIRES
DITEK UNIT
NEUTRAL BUS
SERVICE DISCONNECT PANEL
GROUND BUSS
GREEN WIRE
BLACK WIRES
DITEK UNIT
This Surge Protective Device (SPD) is a high performance device, designed to provide protection
for sensitive electronic loads connected to service panels, fire panels, or where the SPD is
directly connected to the electronic device. Maximum protection will only be achieved if the SPD
is properly installed. Please read and follow the installation instructions carefully.
NOTICE: This SPD should be installed and grounded, by a licensed contractor, per the applicable
requirements of the NEC and the following instructions.
APPLICATION:
Type 1 and Type 2 SPD for hardwired parallel installations on 3-Phase Delta circuits.
Expected system voltages:
DTK-2403CMXPLUS L1-G = 240VAC, L2-G = 240VAC, L3-G = 240VAC
DTK-4803CMXPLUS L1-G = 480VAC, L2-G = 480VAC, L3-G = 480VAC
DTK-6003CMXPLUS L1-G = 600VAC, L2-G = 600VAC, L3-G = 600VAC
INSTRUCTIONS:
Caution: Measure all voltages to insure applied voltage does not exceed the voltage rating of the
unit. Improper installation voids the warranty. This unit must be connected in parallel with the
equipment to be connected.
Warning: No Serviceable Parts-Attention:Aucune pièce remplaçable ou réparable
For Use Only With A Flexible Conduit System Or Direct Connection To Panel
NOTE: Suitable for use on a circuit capable of delivering not more than 10,000 rms symmetrical
Amperes, when protected by a 20 Ampere circuit breaker rated:DTK-2403CMXPLUS=240 Volts min.
DTK-4803CMXPLUS=480 Volts min., DTK-6003CMXPLUS=600 Volts min.
1. Turn off main power before beginning the installation.
2. Remove the front cover from panel.
3. Remove the 3/4" knockout on the side of the panel box.
4. Unscrew nut from unit, keep gasket in place.
5. Feed all wires through the knockout hole then through nut. Tighten the nut to secure the unit
to the panel, make sure gasket compresses between panel and DTK unit.
6. Connect the green (Ground) wire to the ground bus.
7. Always have one common ground per system to eliminate the possibility of a differential in
ground potentials.
Ground Resistance Rule: Max ground resistance is 25 ohms, 5 ohms or less is optimum.
This cannot be an assumed value and must be measured to assure proper grounding.
8. Connect the phase (Black) wires to the load side of 3-pole circuit breaker or disconnect, making sure
the leads are as short as possible (Ground being the shortest).
9. After all connections have been made and no hazards exist, restore power.
10. This device features an internal protection that will disconnect the surge protective component but
will maintain power to the load - now unprotected. If this situation is undesirable for the application,
follow the manufacturer’s instructions for replacing the device.
NOTE: The LED on the unit must be on, if the LED is off than surge protection is compromised and
the unit must be replaced.
DITEK Technical Support Available 24/7
1-888-472-6100 www.diteksurgeprotection.com