Technical data

Ichill 200CX EVO rev 1.1 14/11/2013
Pag. 10 of 151
14
domestic hot water temperature 2
SAn2
15
solar panel temperature
SoLE
16
condenser temperature
Cdt1 circuit 1
Cdt2 circuit 2
17
condenser pressure
CdP1 circuit 1
CdP2 circuit 2
18
evaporator pressure
LP1 circuit 1
LP2 circuit 2
19
compressor oil pressure
20
real time clock
3.2 FORCED READ - OUT OF THE TOP AND BOTTOM DISPLAY
The dP03 parameter allows to have a pre-defined visualization.
dP03=0
The visualization is defined by parameters dP01 and dP02
dP03 = 1
Top display:
Evaporator water inlet temperature, Ein label.
Bottom display:
Evaporator 1 water outlet temperature, label Out1 or evaporator 2 water outlet temperature, label Out2
dP03 = 2
Top display:
Condenser 1 water inlet temperature, label CIn1 or Condenser 2 water inlet temperature, label CIn2
Bottom display
Condenser 1 water outlet temperature, label COu1 or condenser 2 water outlet temperature, label COu2
dP03 = 3
Top display of the circuit 1:
Condenser temperature Cdt1 / pressure CdP1 or Condenser temperature Cdt2 / pressure CdP2
Bottom display of the circuit 1
Evaporator pressure probe LP1 or Evaporator pressure probe LP2
3.3 VICX620: REMOTE TERMINAL 1 VISUALIZATION
If dP04=0 the display has the same visualization of the Ichill.
If dP04=1 upper display visualizes the temperature measured by the probe mounted in the remote terminal
1 (remote terminal must have internal temperature sensor)
3.4 VICX620: REMOTE TERMINAL 2 VISUALIZATION
If dP05=0 the display has the same visualization of the Ichill.
If dP05=1 upper display visualizes the temperature measured by the probe mounted in the remote terminal 2
(remote terminal must have internal temperature sensor)
3.5 DISPLAY VISUALIZATION IN CONDENSIG UNIT
If the Ichill is used to control a condensing unit (CF03=1):
and a digital input has to be configured as “cooling request”; in case of cooling request the
display shows “OnC”
and a digital input has to be configured as “heating request”; in case of heating request the
display shows “OnH”