Technical data

Ichill 200CX EVO rev 1.1 14/11/2013
Pag. 109 of 151
Label on alarm
visualization menu
ACP1 (Condenser 1 pump maintenance)
ACP1 (Condenser 2 pump maintenance)
Origin
Pump running hours > Hour counter setpoint
Reset
Hour reset in function menu
Restart
Manual
Symbol
On the display the symbol
is blinking
Action
Alarm relay + buzzer ON
Regulation
Action
Only display warning messages
Loads
Not changed
ASAn Domestic hot water pump mintenance
Label on alarm
visualization menu
ASAn (Domestic hot water pump maintenance)
Origin
Pump running hours > Hour counter setpoint
Reset
Hour reset in function menu
Restart
Manual
Symbol
On the display the symbol
is blinking
Action
Alarm relay + buzzer ON
Regulation
Action
Only display warning messages
Loads
Not changed
ASUn Solar panel water pump mintenance
Label on alarm
visualization menu
ASUn (Domestic hot water pump maintenance)
Origin
Pump running hours > Hour counter setpoint
Reset
Hour reset in function menu
Restart
Manual
Symbol
On the display the symbol
is blinking
Action
Alarm relay + buzzer ON
Regulation
Action
Only display warning messages
Loads
Not changed
ALSF Phase Sequence
Label on alarm
visualization menu
ALSF
Origin
Phase sequence digital input active
Reset
Phase sequence digital input not active
Restart
Automatic
Symbol
blinkling
Action
Alarm relay + buzzer ON
Regulation
Loads
OFF
ASLA Failed Communication With I/O Expansion
Label on alarm
visualization menu
ASLA
Origin
Failed communication with I/O expansion