Technical data
Ichill 200CX EVO rev 1.1 14/11/2013
Pag. 122 of 151
Sd 15
Summer outside temperature analog 2
-50.0
-58
110.0
230
°C
°F
Dec
int
Sd 16
Winter outside temperature analog 2
-50.0
-58
110.0
230
°C
°F
Dec
int
Sd 17
Summer outside temp. differential analog 2
-30.0
-54
30.0
54
°C
°F
Dec
int
Sd 18
Winter outside temp. differential analog 2
-30.0
-54
30.0
54
°C
°F
Dec
int
Sd 19
Dynamic set point: summer offset relay AUX1
-30.0
-54
30.0
54
°C
°F
Dec
int
Sd 20
Dynamic set point: winter offset relay AUX1
-30.0
-54
30.0
54
°C
°F
Dec
int
Sd 21
Summer outside temperature relay AUX1
-50.0
-58
110.0
230
°C
°F
Dec
int
Sd 22
Winter outside temperature relay AUX1
-50.0
-58
110.0
230
°C
°F
Dec
int
Sd 23
Summer temperature differential relay AUX1
-30.0
-54
30.0
54
°C
°F
Dec
int
Sd 24
Winter temperature differential relay AUX1
-30.0
-54
30.0
54
°C
°F
Dec
int
Sd 25
Dynamic set point: summer offset relay AUX2
-30.0
-54
30.0
54
°C
°F
Dec
int
Sd 26
Dynamic set point: winter offset relay AUX2
-30.0
-54
30.0
54
°C
°F
Dec
int
Sd 27
Summer outside temperature relay AUX2
-50.0
-58
110.0
230
°C
°F
Dec
int
Sd 28
Winter outside temperature relay AUX2
-50.0
-58
110.0
230
°C
°F
Dec
int
Sd 29
Summer temperature differential relay AUX2
-30.0
-54
30.0
54
°C
°F
Dec
int
Sd 30
Winter temperature differential relay AUX2
-30.0
-54
30.0
54
°C
°F
Dec
int
Parameter Description min max M. u. Resolution
ES 1 Start of the Time band 1 (0÷24) 0 24.00 Hr 10 Min
ES 2 End of the Time Band 1 (0÷24) 0 24.00 Hr 10 Min
ES 3 Start of the Time band 2 (0÷24) 0 24.00 Hr 10 Min
ES 4 End of the Time Band 2 (0÷24) 0 24.00 Hr 10 Min
ES 5 Start of the Time band 3 (0÷24) 0 24.00 Hr 10 Min
ES 6 End of the Time Band 3 (0÷24) 0 24.00 Hr 10 Min
ES 7 Monday: energy saving activated
Automatic unit on-off
0 - 0 7 - 7
ES 8 Tuesday energy saving activated
Automatic unit on-off
0 - 0 7 - 7
ES 9 Wednesday energy saving activated
Automatic unit on-off
0 - 0 7 - 7
ES 10 Thursday energy saving activated
Automatic unit on-off
0 - 0 7 - 7
ES 11 Friday energy saving activated
Automatic unit on-off
0 - 0 7 - 7
ES 12 Saturday energy saving activated
Automatic unit on-off
0 - 0 7 - 7
ES 13 Sunday energy saving activated
Automatic unit on-off
0 - 0 7 - 7
ES 14 Energy Saving setpoint offset in chiller mode -30.0
-54
30.0
54
°C
°F
Dec
int
ES 15 Energy Saving differential in chiller mode 0.1
0
25.0
45
°C
°F
Dec
int
ES 16 Energy Saving setpoint offset in heat pump mode -30.0
-54
30.0
54
°C
°F
Dec
int
ES 17 Energy Saving differential in heat pump mode 0.1
0
25.0
45
°C
°F
Dec
int
ES 18 Maximum ON time when the unit is switched on by keyboard starting from
OFF state by RTC
0= Not enabled
1 250 10 min min
ES 19 Start of the Time band 1 Sanitary water (0÷24) 0 24.00 Hr 10 Min
ES 20 End of the Time band 1 Sanitary water (0÷24) 0 24.00 Hr 10 Min
ES 21 Start of the Time band 2 Sanitary water (0÷24) 0 24.00 Hr 10 Min
ES 22 End of the Time band 2 Sanitary water (0÷24) 0 24.00 Hr 10 Min
ES 23 Start of the Time band 3 Sanitary water (0÷24) 0 24.00 Hr 10 Min
ES 24 End of the Time band 3 Sanitary water (0÷24) 0 24.00 Hr 10 Min
ES 25 Monday: Sanitary water 2
n
d
set point activation 0 7
ES 26 Tuesday: Sanitary water 2
n
d
set point activation 0 7
ES 27 Wednesday: Sanitary water 2
n
d
set point activation 0 7
ES 28 Thursday: Sanitary water 2
n
d
set point activation 0 7