54. ELECTRICAL CONNECTIONS
The instrument is provided with:
2 removable terminal blocks MOLEX MICROFIT 14 and 18 ways for power supply voltage / digital and
analogue inputs and modulating outputs
1 removable terminal blocks AMP 12 ways for the relay outputs
5 ways connector for TTL RS485 interface outputs
Wiring cables:
CWCXA15-KIT IC206CX 1.5mt
CWCXA30-KIT IC206CX 3.0mt
CWCXB15-KIT IC208CX 1.5mt
CWCXB30-KIT IC208CX 3.0mt
Wire size:
signal cable AWG 24
power supply cable AWG 22
relay output AWG 17
General notes:
Check the connecitons and the line voltage before turning on the power supply.
Keep low voltage cables, such as analogue/digital inputs/outputs and probes, away from power cables
and terminals.
Respect the maximum load current of each relay output, in case of power loads use filtered contactors.
55. ACCESSORIES
55.1 MONOPHASE FAN CONTROL: 230VAC AND CUT PHASE CONTROL
Models XV05PK XV10PK XV22PK
Power 500W 1000W 2200W
Ampere 2A 4A 9.5A
Power supply
230Vac Input
0 - 230Vac output
-10 - 65°C Operating temperature