Technical data

Ichill 200CX EVO rev 1.1 14/11/2013
Pag. 30 of 151
60. Capacity step valve 2 compressor 2
61. Capacity step valve 3 compressor 2
62. By-pass gas valve compressor 2
63. Direct start: compressor 3 relay
PW start: relay PW 1 of the compressor3
64. PW start: relay PW 2 of the compressor 3
65. Capacity step valve 1 compressor 3
66. Capacity step valve 2 compressor 3
67. Capacity step valve 3 compressor 3
68. By-pass gas valve compressor 3
69. Direct start: compressor 4 relay
PW start: PW 1 of the compressor 4
70. PW start: relay PW 2 of the compressor 4
71. Capacity step valve 1 of the compressor 4
72. Capacity step valve 2 of the compressor 4
73. Capacity step valve 3 of the compressor 4
74. By-pass gas valve compressor 4
Proportional output configuration OUT 1 and OUT 2 (0 ÷ 10 Vdc)
0 Not enabled
1 Modulated evaporator water pump
2 Modulated Free cooling valve
3 not used
4 Auxiliary output 0÷10V n° 1
5 Auxiliary output 0÷10V n° 2
6 Proportional output for modulating compressor 1
7 Proportional output for modulating compressor 2
8 Condenser fan circuit 1
9 Condenser fan circuit 2
After selection number 9 it is possible to configure the analog output as digital output with the same meaning
of the relays configuration; every analog output can be configured from “o 1” to “c50” (see relay
configuration table).
Proportional output configuration OUT 3 and OUT 4 (0 ÷ 10 Vdc/PWM)
0 Not enabled
1 Modulated evaporator water pump (0..10 Vdc)
2 Modulated Free cooling valve (0..10 Vdc)
3 not used
4 Auxiliary output 0÷10V n° 1 (0..10 Vdc)
5 Auxiliary output 0÷10V n° 2 (0..10 Vdc)
6 Proportional output for modulating compressor 1 (0..10 Vdc)
7 Proportional output for modulating compressor 2 (0..10 Vdc)
8 Condenser fan circuit 1 (0..10 Vdc)
9 Condenser fan circuit 2 (0..10 Vdc)
10 Condenser fan circuit 1 (PWM)
11 Condenser fan circuit 2 (PWM)
After selection number 11 it is possible to configure the analog output as digital output with the same
meaning of the relays configuration; every analog output can be configured from “o 1” to “c50” (see relay
configuration table).
OTHER OUTPUTS
o LAN to connect I/O Expansion
o Serial output TTL to connect the HotKey, or Personal computer (through hardware interface) for
parameters programming with Wizmate software, or XJ485RS device for connection to XWEB
supervisor system.