Technical data
Ichill 200CX EVO rev 1.1 14/11/2013
Pag. 43 of 151
0 %
25 %
50 %
75 %
100 %
CO06 = 1 direct action
Eg: compressor with 3 capacity step.
Capacity 25% 50% 75% 100%
Compr.
Compressor ON Compressor ON Compressor ON Compressor ON
Out relay
Cap. step 1 ON Cap. step 1 ON Cap. step 1 ON Cap. step 1 OFF
Out relay
Cap. step 2 OFF Cap. step 2 ON Cap. step 2 ON Cap. step 2 OFF
Out relay
Cap. step 3 OFF Cap. step 3 OFF Cap. step 3 ON Cap. step 3 OFF
Direct action with sequential step
Compressor Cap.
step 1
Cap.
step 2
Cap.
step 3
Power
0 %
25 %
50 %
75 %
100 %
CO06 = 2 inverse action
Eg: compressor with 3 capacity step.
Capacity 25% 50% 75% 100%
Compr.
Compressor ON Compressor ON Compressor ON Compressor ON
Out relay
Cap. step 1 ON Cap. step 1 ON Cap. step 1 ON Cap. step 1 OFF
Out relay
Cap. step 2 ON Cap. step 2 ON Cap. step 2 OFF Cap. step 2 OFF
Out relay
Cap. step 3 ON Cap. step 3 OFF Cap. step 3 OFF Cap. step 3 OFF
Inverse action with sequential step
Compressor Cap.
step 1
Cap.
step 2
Cap.
step 3
Power
0 %
25 %
50 %
75 %
100 %
CO06 = 3 Continuous steps and direct action
Eg: compressor with 3 capacity step.
Capacity 25% 50% 75% 100%
Compr.
compressor ON compressor ON compressor ON compressor ON
Out relay
Cap. step 3 OFF Cap. step 3 ON Cap. step 3 ON Cap. step 3 ON
Out relay
Cap. step 2 OFF Cap. step 2 OFF Cap. step 2 ON Cap. step 2 ON
Out relay
Cap. step OFF Cap. step OFF Cap. step 1 OFF Cap. step 1 ON
Direct action with sequential step