• the parameter CO62≠0 the compressor is forced to works at maximum power and then it modulates
the power according to the regulation request
It is possible to limit the output % of the inverter compressor in Chiller, Heat pump and Sanitary hot water:
o maximum % output inverter in Chiller (parameter CO79)
o maximum % output inverter in Heat pump (parameter CO80)
o maximum % output inverter in Sanitary hot water (parameter CO81)
COMPRESSOR INVERTER CONTROLLED OPERATING MODE: CHILLER
At the start up the compressor is forced to work at CO61 speed for CO60 seconds.
COMPRESSOR INVERTER CONTROLLED OPERATING MODE: HEAT PUMP
At the start up the compressor is forced to work at CO61 speed for CO60 seconds.