Technical data

Ichill 200CX EVO rev 1.1 14/11/2013
Pag. 85 of 151
Winter operation mode:
If the machine is switched on and external temperature or condenser temperature/pressure is inside the
differential:
machine in chiller and temperature/pressure inside the differential dF29: exchanger 2 ON
machine in chiller and temperature/pressure inside the differential dF30: exchanger 1 and exchanger
2 ON
machine in heat pump and temperature/pressure inside the differential dF33: exchanger 2 ON
machine in heat pump and temperature/pressure inside the differential dF34: exchanger 1 and
exchanger 2 ON
In chiller when first compressor starts both exchangers are ON for dF36 time; after this time the regulation
follows diagrams above.
If dF36=0 the regulation follows diagrams above also at the start up.
In defrost this regulation is disabled.
In STD-BY or remote OFF the status of the exchangers is hybrid exchanger 1=ON, hybrid exchanger
2=OFF.
The set point is related to the status of the machine:
if the machine is producing cooled water and domestic hot water, reference set point is chiller set
point
if the machine is producing only domestic hot water, reference set point is heat pump set point
43. GEOTHERMAL FREE COOLING
Outputs managed: