23
9.5 Connect several loads
(only MSI1800T, MSI1800TOE)
The device is equipped with galvanic isolation when delivered. For the safe opera-
tion of multiple loads, it is essential that a circuit breaker (residual current circuit
breaker) is built into the socket distribution circuit, see sample circuit diagram in
fig. 0, page 7.
Sample circuit diagram legend:
!
Install a residual current circuit breaker in the socket distribution circuit.
9.6 Connect earthing strap (only MSI1800T,
MSI1800TOE)
MSI1800T: fig. 7 8. page 5
MSI1800TOE: fig. 8 8. page 5
Screw the earthing screw out of the upper hole.
Screw the screw in the lower hole in.
No. in
fig. 0,
page 7
Explanation
1 230 Vw power source
2 Additional devices, e.g. battery charger, refrigerator
3 DC power source (battery)
4Inverter
5 Grounding bridge set (At delivery: not set, shown by dotted line)
6 Circuit breaker (residual current circuit breaker)
7 Socket distribution circuit for load unit
WARNING! Danger of electrocution
If you wish to connect more than one load unit to the inverter and install
a socket distribution circuit, you must arrange a circuit breaker (residual
current circuit breaker) and put an earthing strap in the inverter.