Use inverter SinePower
28
10.3 Configuring the inverter
I
You can adjust the device with the help of he dip-switch (fig. 6 4, page 4 to
fig. 8 4, page 5).
Setting the mains voltage
You can set the mains voltage using the S1 and S2 dip switches.
Setting the mains frequency
!
You can set the mains frequency using the S3 dip switch.
NOTE
Settings can only be made using the dip switch if the S8 dip switch S8 is
in the position ‘On’.
Dip switch
Mains voltage S1 S2
200 V Off Off
220 V On Off
230 V Off On
240 V On On
WARNING! Danger of electrocution
Only adjust the S3 DIP switch when the respective frequency for the
output voltage should be used.
Dip switch
Net frequency S3
50 Hz Off
60 Hz On