Air Conditioner User Manual

11
INSTALLATION INSTRUCTIONS
System Model 39626.501 & 39626.506*
Nominal BTU Capacity 26,000
Volts/Phase/Hertz (each circuit) 115 AC / 1 / 60
Run Amps Comp (Circuit 1 = 10.1) (Circuit 2 = 9.8)
LRA Compressor (Circuit 1 = 59.0) (Circuit 2 = 59.0)
Total Blwr/Fan Motor Run Amps 8.5 (Circuit 1)
Total Blwr/Fan Motor LRA Amps 18.0 (Circuit 1)
Duct Static - Min. ( In. Water Column) 0.40
Duct Static - Max. ( In. Water Column) 1.20
Generator Size Per/Unit - Min. *** 7.5K
Wire Size (Up to 24 ft.) ** (Circuit 1) No. 10 AWG Copper Conductors)
(Suggested) (Circuit 2) No. 12 AWG Copper Conductors)
Circuit Protection (Circuit 1) 25Amp
Time Delay Fuse or (Circuit 2) 15Amp
HACR Circuit Breaker
Control Voltage 12V DC
Refrigerant R-22
System Refrigerant Charge (Circuit 1 = 46.5) (Circuit 2 = 38.5)
Size (In Inches) Width Height Depth
46 18 22
Installed 205 Pounds
Weight
2.9 SPECIFICATIONS - AIR CONDITIONER
2. 8 WIRING DIAGRAM 39626.501 & 39626.506
**
Models ending with .506 suffix and manufactured with "SIDE AIR DISCHARGE".
For wire lengths over 24 ft. consult the National Electric Code for proper sizing.
The Manufacturer gives only general guidelines for generator requirements. These generator
requirements come from experiences consumers have with our equipment in field applications.
When sizing the generator, the total electrical power must be taken into consideration. Keep in
mind that generators lose power because of altitude increases above sea level , high outdoor
temperatures and lack of maintenance.
*
***