Operating instructions
71
The cable assembly for the Roof-Top Heat Pump is avail-
able in 15, 25 and 30 foot lengths. This cable assembly has
a male connector on one end (thermostat connection) and
a female connector on the other end (heat pump connec-
tion).
The cable assembly has 10 wires. The arrow on each
connector designates Pin 1.
To check the cable assembly, disconnect each end of
the cable assembly and check for continuity on each wire
in the assembly.
Also, check each connector for bent pins or loose wires.
Each wire has a receptacle that snaps into the connector.
CHANGEOVER THERMOSTATCHANGEOVER THERMOSTAT
CHANGEOVER THERMOSTATCHANGEOVER THERMOSTAT
CHANGEOVER THERMOSTAT
11E. CHANGEOVER THERMOSTAT
The changeover thermostat is a capillary tube/bellows-
type switch. Its function is to allow the compressor to
operate only when outside ambient is 40°F. or warmer.
To check the changeover thermostat, first verify the air
temperature at the capillary tube. If the temperatures are
above 45°F., continuity should be between terminals 2 to 3
and no continuity between terminals 2 to 1. For tempera-
tures below 40°F., continuity should be between terminals
2 to 1 and no continuity between terminals 2 to 3.
NOTE: A defective changeover thermostat can keep
the compressor from operating in the COOL or HEAT
PUMP modes.
12E. RELAY BOARD
The relay board consists of a transformer, compressor
relay, two fan relays and other components. If any one of
these are defective, the complete relay board must be
replaced.
The relay board completes circuits to the fan motor and
compressor depending on what mode switch and tem-
perature setting is on the thermostat.
Remove the cover from the electric box and verify the
red wire is on terminal RC, black wire is on terminal G, blue
wire is on terminal H and yellow wire is on terminal Y.
With AC power to the relay board, check between
terminals RC and G or H. There should be 12 volts DC. If
no voltage is detected, the transformer on the relay board
is defective. Replace the relay board.
If 12 volts DC is available, disconnect power to the heat
pump and remove the HI FAN wire (black) and the LOW
FAN wire (red) and the compressor wire (large black) from
the NO terminal on the compressor relay on the relay
board.
ROOF-TOP HEAT PUMP CABLE ASSEMBLYROOF-TOP HEAT PUMP CABLE ASSEMBLY
ROOF-TOP HEAT PUMP CABLE ASSEMBLYROOF-TOP HEAT PUMP CABLE ASSEMBLY
ROOF-TOP HEAT PUMP CABLE ASSEMBLY