Operating instructions
73
14E. REVERSING VALVE
The reversing valve is the heart of a heat pump. It directs
refrigerant flow to the coils to achieve proper direction of
flow that allows the same system to supply heated or
cooled air to enter the inside atmosphere of the structure
according to occupants' desires.
The reversing valve's solenoid can be energized in
either HEAT or COOL mode of operation. Duo-Therm Heat
Pumps that are roof-mounted units have the solenoid
energized in the COOL mode of operation.
One way to check the reversing valve is to feel the
refrigerant line at the top of the inside coil. In the COOL
mode, this line will be cool or cold to the touch. In the HEAT
mode, this line will be warm or hot to the touch. If you do not
achieve these results, direction of refrigerant flow is not
correct. Check the relay (see Section 4.10), wiring (see
Section 2.3) and thermostat (see Section 4.2). Refer to
Section 1 for Principals of Heat Pump Operation.
The ohms resistance of the reversing valve solenoid coil
is approximately 465 ohms plus or minus (±) 10%.
15E. RELAY, FAN SPEED (DPST)
The relay is a double pole, single throw and controls the fan
motor in the roof mounted unit. When the AUX HEAT mode
is selected or the outside temperature is too cold for HEAT
PUMP operation and automatically goes to auxiliary opera-
tion, the relay will interrupt the circuit to the fan motor.
When COOL, OFF and HEAT PUMP modes are se-
lected, the relay coil is not energized. When AUX. HEAT
mode is selected the relay coil is energized with 12V DC.
To check the relay, first remove the wires from COM
and NC terminals. Next verify the relay coil is not energized
(no DC power), continuity should exist between terminals
COM and NC and no continuity between terminals COM
and NO. Next energize the relay coil with DC volts (10 to
16). Continuity should exist between terminals COM and
NO and no continuity between COM and NC. If the above
checks are correct, the relay is good – DO NOT replace it.
If the above checks are not correct, the relay is defective
and should be replaced.
NOTE: Verify the thermostat is wired properly from the
furnace, as incorrect polarity on the furnace thermostat
wires will energize the relay coil and keep the fan motor
from operating in the roof mounted unit.