Operating instructions
85
D.D.
D.D.
D.
MODEL 39224.601MODEL 39224.601
MODEL 39224.601MODEL 39224.601
MODEL 39224.601
This thermostat is designed to operate DC volt controlled
air conditioner systems and an independent heat system.
It is a manual changeover thermostat between heating and
cooling. It also incorporates time delay circuitry to protect
against system short cycling. This thermostat has delay
circuitry on start-up so Circuit 1 compressor starts after fan
motors, then delay circuitry for Circuit 2 compressor start.
It is an electronic thermostat with three pushbuttons (MODE,
SET TEMPERATURE UP AND DOWN) and an LCD
(Liquid Crystal Display).
To check the thermostat, first verify the wiring to it is
correct. A two-conductor cable, 18 to 22 AWG is required
for the DC volt power source. This MUST be routed to the
system at the thermostat. There is a nine-terminal block on
the back of the thermostat.
Looking at the back of the thermostat, the terminal desig-
nation from right-to-left is
Y2Y2
Y2Y2
Y2,
Y1Y1
Y1Y1
Y1,
WW
WW
W,
RR
RR
R,
BB
BB
B,
GHGH
GHGH
GH,
GL GL
GL GL
GL and the
last two are not designated. DC volt supply wires into
terminal R, positive (+); and terminal B, negative (–). There
is a five-wire (white, yellow, black orange and blue) harness
assembly that wires into the terminal block also. White
goes to
Y2Y2
Y2Y2
Y2, yellow goes to
Y1Y1
Y1Y1
Y1, black goes to
BB
BB
B (this
makes two wires on this terminal), orange goes to
GHGH
GHGH
GH, and
blue goes to
GLGL
GLGL
GL. If a furnace is wired to the thermostat the
two furnace thermostat wires
MUSTMUST
MUSTMUST
MUST be wired correctly.
The furnace has two wires for thermostat connections. One
wire should be marked 12V DC or (+) and the other wire
may be unmarked, or labeled "thermostat". The wire marked
12V DC or (+) must be wired to terminal
WW
WW
W. The unmarked
wire (or one labeled "thermostat") must be wired to
BB
BB
B
terminal (this will be the third wire to this terminal).
6
8
0
F
by Dometic
THERMOSTAT
Display delayed 1 minute at turn on.
Actual
Cool
Heat
Set Temperature
COOL
HEAT
OFF
FAN
HIGH
LOW
HIGH
LOW
AUTO
ON
MODE UP DOWN
®
THERMOSTATTHERMOSTAT
THERMOSTATTHERMOSTAT
THERMOSTAT
BACK OF THERMOSTATBACK OF THERMOSTAT
BACK OF THERMOSTATBACK OF THERMOSTAT
BACK OF THERMOSTAT
To check the thermostat, first verify positive (+) DC is to
terminal
RR
RR
R and negative (–) is to terminal
BB
BB
B, at the back of the
thermostat. Operating range is 10 to 16 volts DC. NOTE: To
check voltage between terminals, at the back of the thermo-
stat, place the negative (–) lead from the voltmeter to terminal
BB
BB
B and the positive (+) lead from the voltmeter to the ACTIVE
terminal.
With the SYSTEM switch to COOL and FAN switch to HIGH
AUTO and room temperature ABOVE setpoint temperature,
you should have voltage between terminal
BB
BB
B (black wire) to
terminal
Y1Y1
Y1Y1
Y1 (yellow wire) and terminal
BB
BB
B (black wire) to terminal
GHGH
GHGH
GH (orange wire). You should NOT have voltage between
terminal
BB
BB
B (black wire) to terminals
GLGL
GLGL
GL (blue wire) and
WW
WW
W. With
room temperature BELOW setpoint temperature you should
NOT have voltage between terminal
BB
BB
B (black wire) to terminals
Y1Y1
Y1Y1
Y1,
Y2Y2
Y2Y2
Y2,
GLGL
GLGL
GL,
GHGH
GHGH
GH or
WW
WW
W.
NOTENOTE
NOTENOTE
NOTE: When setpoint temperature is changed above or below
room temperature, there will be a three minute delay in "active"
terminals. If setpoint temperature is more than two degrees
from room temperature, there will be a thirty second delay to
Y2Y2
Y2Y2
Y2
terminal after
Y1Y1
Y1Y1
Y1 terminal is active.
With SYSTEM switch to COOL and FAN switch to AUTO LOW,
and room temperature is above setpoint temperature, you
should have voltage between terminal
BB
BB
B (black wire) to terminal
Y1Y1
Y1Y1
Y1 (yellow wire) and terminal
BB
BB
B (black wire) to terminal
GLGL
GLGL
GL (blue
wire). You should
NOTNOT
NOTNOT
NOT have voltage between terminal
BB
BB
B (black
wire) to terminals
GHGH
GHGH
GH (orange) and
WW
WW
W. With room temperature
BELOW setpoint temperature you should NOT have voltage
between terminal
BB
BB
B (black wire) to terminals
Y1Y1
Y1Y1
Y1,
Y2Y2
Y2Y2
Y2,
GLGL
GLGL
GL,
GHGH
GHGH
GH
and
WW
WW
W.
NOTENOTE
NOTENOTE
NOTE: When setpoint temperature is changed above or below
room temperature, there will be a three minute delay in "active"
terminals. If setpoint temperature is more than two degrees
from room temperature, there will be a thirty second delay to
Y2Y2
Y2Y2
Y2
terminal after
Y1Y1
Y1Y1
Y1 terminal is active.