Operating instructions

91
BIMETALBIMETAL
BIMETALBIMETAL
BIMETAL
This thermostat is designed to operate 12V DC single-
stage heat pump and an independent single-stage auxiliary
heat system. It is a manual changeover thermostat be-
tween heating, cooling and auxiliary heat. Operating tem-
peratures for both heating and cooling systems are change-
able to suit the comfort needs of the occupants.
This thermostat is used for a remote wall mounted thermo-
stat. Check the operation. Next, verify the wiring to the
thermostat is correct.
Thermostat Wiring for Dometic Bimetal ThermostatThermostat Wiring for Dometic Bimetal Thermostat
Thermostat Wiring for Dometic Bimetal ThermostatThermostat Wiring for Dometic Bimetal Thermostat
Thermostat Wiring for Dometic Bimetal Thermostat:
Route the ten-conductor cable from the unit to the thermo-
stat location. Leave enough cable to connect to the low
voltage cable. At the thermostat location, leave about six
(6") inches of cable extending through the wall. Plug the
thermostat cable into the thermostat connector cable.
When an auxiliary furnace is used with the heat pump, a two
conductor cable must be routed from the furnace to the
thermostat location. Connect one wire from the furnace to
the violet wires with a wirenut. Connect the other wire from
the furnace to the green wire in the thermostat cable and
secure with a wire nut. Tuck the excess wire back into the
wall and fill opening with insulation to prevent drafts that
could affect the thermostat operation. Secure the thermo-
stat to the wall using the two screws.
NOTE: Verify the heat anticipator is set properly for the
auxiliary furnace. Failure to set the anticipator can cause
incorrect operation or failure of thermostat in AUX HEAT or
HEAT PUMP setting.
CABLE ASSEMBLY CONNECTORCABLE ASSEMBLY CONNECTOR
CABLE ASSEMBLY CONNECTORCABLE ASSEMBLY CONNECTOR
CABLE ASSEMBLY CONNECTOR
Before checking the thermostat for operation, first determine
that the thermostat is receiving DC power from the relay board
then disconnect the cable assembly from the back of the
thermostat.
Next, use a DC voltmeter and check from red wire or Pin 2 on
cable assembly (positive [+] lead from voltmeter) to brown wire
or Pin 7 (negative [–] lead from voltmeter). You should get a
voltage reading of approximately 12V DC. Next, move the
negative (–) lead from the voltmeter to each of the following
wires or pins:
Blue (Pin 6), Yellow (Pin 5), Black (Pin 4) White (Pin 3)Blue (Pin 6), Yellow (Pin 5), Black (Pin 4) White (Pin 3)
Blue (Pin 6), Yellow (Pin 5), Black (Pin 4) White (Pin 3)Blue (Pin 6), Yellow (Pin 5), Black (Pin 4) White (Pin 3)
Blue (Pin 6), Yellow (Pin 5), Black (Pin 4) White (Pin 3). You
should get a voltage reading of approximately 12V DC on each
wire. This indicates the relay board and cable assembly are
providing proper power and circuits to the thermostat.
NOTENOTE
NOTENOTE
NOTE: Pin 2 (red wire) is positive DC volts when ambient
(outside) air is above 40°F. Pin 1 (violet wire) is positive DC
volts when ambient (outside) air is below 40°F.
If the above voltage checks are correct and the unit does not
operate correctly, check the thermostat.
If the above voltage checks are not as described, check the
relay board and the cable assembly.
To check the thermostat, first remove it from its mounting on the
wall. Then disconnect the thermostat assembly from the cable
assembly in the wall. Now you are ready to do a continuity
check on the thermostat assembly. Place the positive (+) lead
from the ohm meter on red wire (Pin 2) and negative (–) lead
from the ohm meter to the active pin or wire to read continuity.
POLARITY IS IMPORTANT FOR A PROPER CHECK TO BEPOLARITY IS IMPORTANT FOR A PROPER CHECK TO BE
POLARITY IS IMPORTANT FOR A PROPER CHECK TO BEPOLARITY IS IMPORTANT FOR A PROPER CHECK TO BE
POLARITY IS IMPORTANT FOR A PROPER CHECK TO BE
DONEDONE
DONEDONE
DONE.
With System Switch in COOL, Fan Switch in HI AUTO and
room temperature ABOVE setpoint temperature, you should
have continuity between red wire (Pin 2) to black wire (Pin 4),
yellow wire (Pin 5) and blue wire (Pin 6). You should NOT have
continuity between red wire to violet or white wires.