Operating instructions

93
With System Switch in AUX HEAT, Fan Switch in LOW AUTO
and room temperature ABOVE setpoint temperature, you
should NOT have continuity between red wire to violet, white,
black, yellow or blue wires. With room temperature BELOW
setpoint temperature, you should have continuity between
violet wire (Pin 1) and green wire. You should NOT have
continuity between red wire to violet, white, black, yellow or
blue wires.
With System Switch in AUX HEAT, Fan Switch in LOW ON and
room temperature ABOVE setpoint temperature, you should
have continuity between red wire (Pin 2) to black wire (Pin 4).
You should NOT have continuity between red wire to violet,
white, yellow or blue wires. With room temperature BELOW
setpoint temperature, you should have continuity between red
wire (Pin 2) to black wire )Pin 4) and between violet wire (Pin
1) to green wire. You should NOT have continuity between red
wire to violet, white, yellow or blue wires.
With System Switch in AUX HEAT, Fan Switch in HI ON and
room temperature ABOVE setpoint temperature, you should
have continuity between red wire (Pin 2) to black wire (Pin 4)
and blue wire (Pin 6). You should NOT have continuity between
red wire to violet, white or yellow wires. With room temperature
BELOW setpoint temperature, you should have continuity
between red wire (Pin 2) to black wire (Pin 4) and blue wire (Pin
6) and between violet wire (Pin 1) and green wire. You should
NOT have continuity between red wire to violet, white or yellow
wires.
LO OnLO On
LO OnLO On
LO On
Above
Below
HI AutoHI Auto
HI AutoHI Auto
HI Auto
Above
Below
LO AutoLO Auto
LO AutoLO Auto
LO Auto
Above
Below
Above
Below
HI OnHI On
HI OnHI On
HI On
LO OnLO On
LO OnLO On
LO On
Above
Below
HI AutoHI Auto
HI AutoHI Auto
HI Auto
Above
Below
LO AutoLO Auto
LO AutoLO Auto
LO Auto
Above
Below
Above
Below
HI OnHI On
HI OnHI On
HI On
LO OnLO On
LO OnLO On
LO On
Above
Below
HI AutoHI Auto
HI AutoHI Auto
HI Auto
Above
Below
LO AutoLO Auto
LO AutoLO Auto
LO Auto
Above
Below
Above
Below
HI OnHI On
HI OnHI On
HI On
LO OnLO On
LO OnLO On
LO On
Above
Below
SystemSystem
SystemSystem
System
SwitchSwitch
SwitchSwitch
Switch
FanFan
FanFan
Fan
SwitchSwitch
SwitchSwitch
Switch
If roomIf room
If roomIf room
If room
Temp. isTemp. is
Temp. isTemp. is
Temp. is
Above/Above/
Above/Above/
Above/
BelowBelow
BelowBelow
Below
setpointsetpoint
setpointsetpoint
setpoint
temp:temp:
temp:temp:
temp:
Pin 3Pin 3
Pin 3Pin 3
Pin 3
WhiteWhite
WhiteWhite
White
Pin 1Pin 1
Pin 1Pin 1
Pin 1
VioletViolet
VioletViolet
Violet
Pin 5Pin 5
Pin 5Pin 5
Pin 5
YellowYellow
YellowYellow
Yellow
Pin 6Pin 6
Pin 6Pin 6
Pin 6
BlueBlue
BlueBlue
Blue
Pin 4Pin 4
Pin 4Pin 4
Pin 4
BlackBlack
BlackBlack
Black
Terminals that are "ON"Terminals that are "ON"
Terminals that are "ON"Terminals that are "ON"
Terminals that are "ON"
SWITCHSWITCH
SWITCHSWITCH
SWITCH
COMBINA-COMBINA-
COMBINA-COMBINA-
COMBINA-
TIONSTIONS
TIONSTIONS
TIONS
HI AutoHI Auto
HI AutoHI Auto
HI Auto
Above
Below
LO AutoLO Auto
LO AutoLO Auto
LO Auto
Above
Below
Above
Below
HI OnHI On
HI OnHI On
HI On
HEAT PUMPAUX HEAT
XXX
XX
XX
X
XXX
XX
X
X
XX
XX
XXX
XX
X
XX
X
X
XX
XX
X
X
COOL
OFF
X
X
X
SWITCH COMBINATIONS AND THEIRSWITCH COMBINATIONS AND THEIR
SWITCH COMBINATIONS AND THEIRSWITCH COMBINATIONS AND THEIR
SWITCH COMBINATIONS AND THEIR
CORRESPONDING "ACTIVE" TERMINALSCORRESPONDING "ACTIVE" TERMINALS
CORRESPONDING "ACTIVE" TERMINALSCORRESPONDING "ACTIVE" TERMINALS
CORRESPONDING "ACTIVE" TERMINALS
To check "ACTIVE" terminals, place the positive (+) lead from
the ohm meter on Pin 2 or red wire and negative (–) lead from
ohm meter to the "active" pin or wire to read continuity.
With System Switch in AUX HEAT and room temperature
BELOW setpoint temperature, continuity will exist between
violet wire and green wire. With room temperature ABOVE
setpoint temperature, continuity will NOT exist between violet
and green wire.