Operating instructions
95
C.C.
C.C.
C.
MODEL 39325.XXX AND 39335.XXX HEATMODEL 39325.XXX AND 39335.XXX HEAT
MODEL 39325.XXX AND 39335.XXX HEATMODEL 39325.XXX AND 39335.XXX HEAT
MODEL 39325.XXX AND 39335.XXX HEAT
PUMPSPUMPS
PUMPSPUMPS
PUMPS
The cable assembly is a ten wire cable with seven of the ten
wires used. The thermostat end has a 10-pin flat connector
with seven positions used.
Pin 1 = Violet Wire
Pin 2 = Red Wire
Pin 3 = White Wire
Pin 4 = Black Wire
Pin 5 = Yellow Wire
Pin 6 = Blue Wire
Pin 7 = Brown Wire
The unit end has the above seven wires stripped and needs
to be wired to the corresponding color of wire in the electric
box of the unit. To check the cable assembly, first unplug
the thermostat end and disconnect each wire at the unit.
Next, check for continuity on each wire such as violet to
violet, red to red, etc. Continuity should be present from
violet to violet, red to red, etc.
Next, check for continuity from one wire to each of the other
wires. NO continuity should be present from one wire to any
other wire in the assembly.
393XX.XXX HEAT PUMP393XX.XXX HEAT PUMP
393XX.XXX HEAT PUMP393XX.XXX HEAT PUMP
393XX.XXX HEAT PUMP
CABLE ASSEMBLYCABLE ASSEMBLY
CABLE ASSEMBLYCABLE ASSEMBLY
CABLE ASSEMBLY
9F. REVERSING VALVE
The reversing valve is the heart of a heat pump. It directs
refrigerant flow to the coils to achieve proper direction of flow
that allows the same system to supply heated or cooled air to
enter the inside atmosphere of the structure according to
occupants' desires.
The reversing valve's solenoid can be energized in either
HEAT or COOL mode of operation. Most Duo-Therm Heat
Pumps have the solenoid energized in the COOL mode of
operation. The Dual (Model 39424) has the solenoid energized
in the HEAT mode of operation.
One way to check the reversing valve is to feel the refrigerant
line at the top of the inside coil. In the COOL mode, this line will
be cool or cold to the touch. In the HEAT mode, this line will be
warm or hot to the touch. If you do not achieve these results,
direction of refrigerant flow is not correct.
The ohms resistance of the reversing valve solenoid coil is
approximately 465 ohms plus or minus (±) 10%. If ohms
reading is within this range, the solenoid coil is good. If ohms
reading is outside this range, replace the solenoid coil.
On Model 39424, verify AC volts are to the solenoid coil when
in HEAT mode. If AC volts are NOT present, verify wiring is
correct and the 9-pin terminal connector is proper; and connec-
tion is completed through it. Next, verify power module board
and the relay are good. If AC volts are present and solenoid coil
is good, but refrigerant flow is not proper, the reversing valve
assembly needs to be replaced.
On all other models verify AC volts is to the solenoid coil when
in COOL mode. If AC volts is NOT present, verify wiring is
correct and the 6-pin terminal connector is proper; and connec-
tion is completed through it. Next, verify power module board
is correct, then verify relay is correct. If AC volts are present
and solenoid coil is good, but the refrigerant flow is not proper,
the reversing valve assembly needs to be replaced.