Operating instructions

96
10F. TRANSFORMER
The transformer supplies low AC volts for the control circuit on
the following air conditioner models:
39025.XXX, 39035.XXX & 39045.XXX39025.XXX, 39035.XXX & 39045.XXX
39025.XXX, 39035.XXX & 39045.XXX39025.XXX, 39035.XXX & 39045.XXX
39025.XXX, 39035.XXX & 39045.XXX
The transformer is a 120 volt AC, 50/60 Hz. primary (line
terminals) with a 24 volt AC secondary (load terminals), and
will handle up to 20 volt-amps.
To check the transformer, first verify 120 volt AC is to the
line terminals. Next, verify at least 24 volt AC is on the load
terminals. If 24 volt AC is present on the load terminals, the
transformer is good. If 24 volt AC is
NOTNOT
NOTNOT
NOT present on the
load terminals and 120 volt AC is present on the line termi-
nals, the transformer is defective.
11F. RELAY BOARD
The relay board is used on heat pump models:
39325.XXX, 39335.XXX & 39424.60139325.XXX, 39335.XXX & 39424.601
39325.XXX, 39335.XXX & 39424.60139325.XXX, 39335.XXX & 39424.601
39325.XXX, 39335.XXX & 39424.601
The relay board consists of a transformer, compressor relay,
two fan relays and other components. If any one of these are
defective, the complete relay board must be replaced.
The relay board completes circuits to the fan motor and
compressor depending on what mode switch and temperature
setting is on the thermostat.
Remove the cover from the electric box and verify the red wire
is on terminal RC, black wire is on terminal G, blue wire is on
terminal H and yellow wire is on terminal Y.
With AC power to the relay board, check between terminals RC
and G or H. There should be 12 volts DC. If no voltage is
detected, the transformer on the relay board is defective.
Replace the relay board.
If 12 volts DC is available, disconnect power to the heat pump
and remove the HI FAN wire (black) and the LOW FAN wire
(red) and the compressor wire (large black) from the NO
terminal on the compressor relay on the relay board.
RELAY BOARDRELAY BOARD
RELAY BOARDRELAY BOARD
RELAY BOARD
Next, remove the red, yellow, black and blue wires from
terminals RC, Y, G and H on the relay board. Place a jumper
from terminal RC to terminal Y. Provide power to the heat
pump. Using an incandescent bulb, check from AC white
terminal (one lead from bulb) to NO terminal on compressor
relay on the relay board (other lead from bulb). The bulb should
illuminate. Remove the jumper and the bulb would NOT
illuminate. Next, place a jumper from terminal RC to terminal G.
Now place one lead from bulb to AC white terminal and the
other lead from bulb to LOW FAN terminal. The bulb should
illuminate. Remove the jumper and the bulb should not illumi-
nate. Next, place a jumper from terminal RC to terminals G and
H. Now place one lead from bulb to AC white terminal and the
other lead from bulb to HIGH FAN. The bulb should illuminate.
Remove the jumper and the bulb should not illuminate. If these
tests are correct, the relay board is good. DO NOT replace it.
If any one of these tests are incorrect, replace the relay board.
13F. CHANGEOVER THERMOSTAT
The changeover thermostat is used on heat pump models:
39325.XXX, 39335.XXX and 39424.60139325.XXX, 39335.XXX and 39424.601
39325.XXX, 39335.XXX and 39424.60139325.XXX, 39335.XXX and 39424.601
39325.XXX, 39335.XXX and 39424.601
The changeover thermostat is a capillary tube/bellows-type
switch. Its function is to allow the compressor to operate only
when outside ambient is 40°F. or warmer.
TB9
Y
TB8
TB7
FREEZE
TB4
RC
TB5
G
TB6
H
RELAY
10 AMP
RELAY
10 AMP
TB1
AC WHT
TB3
FAN HI
TB2
FAN LOW
COM
NO
DOMETIC CORPORATION
ASM.#3104757.004
115V AC
INCANDESCENT
BULB
D.C.
VOLT