To check the changeover thermostat, first verify the air tem-
perature at the capillary tube. If the temperatures are above
45°F., continuity should be between terminals 2 to 3 and no
continuity between terminals 2 to 1. For temperatures below
40°F., continuity should be between terminals 2 to 1 and no
continuity between terminals 2 to 3.
NOTENOTE
NOTENOTE
NOTE: A defective changeover thermostat can keep the
compressor from operating in the COOL or HEAT PUMP
modes.
13F. TIME DELAY RELAY
The time delay relay is used on Model 39424.601. Its purpose
is to provide a thirty second delay of power to Circuit 2 System
after Circuit 1 System. To check the relay, use a voltmeter.
Place one lead of voltmeter to Circuit 1 terminal block
NN
NN
N
(neutral) and the other lead of voltmeter to terminal
11
11
1 of relay.
Thirty seconds after terminal
11
11
1 receives AC volts, move
voltmeter lead to terminal
22
22
2 of relay. AC volts should be
present.
CHANGEOVER THERMOSTATCHANGEOVER THERMOSTAT
CHANGEOVER THERMOSTATCHANGEOVER THERMOSTAT
CHANGEOVER THERMOSTAT
14F. RELAY
A.A.
A.A.
A.
Relay, SPST (single pole/single throw) is used onRelay, SPST (single pole/single throw) is used on
Relay, SPST (single pole/single throw) is used onRelay, SPST (single pole/single throw) is used on
Relay, SPST (single pole/single throw) is used on
Models 39224.601 and 39424.601.Models 39224.601 and 39424.601.
Models 39224.601 and 39424.601.Models 39224.601 and 39424.601.
Models 39224.601 and 39424.601.
On Model 39224.601, it is used to complete the 115 volt AC
circuit to the compressors, high fan and low fan. On Model
39424.601, it is used to complete 115 volt AC to the
reversing valves for Circuit 1 and Circuit 2.
The relay has a DC volt coil. The coil terminals are 1 and
3. When the coil is NOT energized (no power to terminals
1 and 3), no continuity will exist between terminals 4 to 2.
When the coil is energized (power to terminals 1 and 3),
continuity will exist between terminals 4 to 2.
B.B.
B.B.
B.
Relay, SPDT (single pole/double throw) is used onRelay, SPDT (single pole/double throw) is used on
Relay, SPDT (single pole/double throw) is used onRelay, SPDT (single pole/double throw) is used on
Relay, SPDT (single pole/double throw) is used on
Models 39325.XXX and 39335.XXXModels 39325.XXX and 39335.XXX
Models 39325.XXX and 39335.XXXModels 39325.XXX and 39335.XXX
Models 39325.XXX and 39335.XXX.
On Model 39325.XXX it is used to complete the 115 volt AC
circuit to the reversing valve.
On Model 39335.XXX is used to complete the 115 volt AC
circuit to the reversing valve and to the furnace blower relay
coil. The relay has a DC volt coil.
Terminals 1 and 3 are the coil terminals. When the coil
(terminals 1 and 3) is NOT energized (no power to termi-
nals 1 and 3), continuity should exist between terminals 4
to 5; and no continuity between terminals 2 to 4.
When the coil (terminals 1 and
3) is energized (power to termi-
nals 1 and 3), continuity should
exist between terminals 2 to 4
and no continuity between ter-
minals 4 to 5.