Operating instructions

99
F.F.
F.F.
F.
Relay, SPDT (single pole/double throw) is used onRelay, SPDT (single pole/double throw) is used on
Relay, SPDT (single pole/double throw) is used onRelay, SPDT (single pole/double throw) is used on
Relay, SPDT (single pole/double throw) is used on
Models 390XX.XXX. Models 390XX.XXX.
Models 390XX.XXX. Models 390XX.XXX.
Models 390XX.XXX. It controls the fan motor.
The relay has a 24 volt AC coil. To check the relay, first
verify all AC volts have been turned off to the unit.
Next, remove the wires from COM and NC terminals.
Verify the relay coil is not energized (no AC power).
Continuity should exist between terminals COM and NO.
Next, energize the relay coil with 24 volts AC. Continuity
should exist between terminals COM and NO and no
continuity between COM and NC. If the above checks are
correct, the relay is good – DO NOT replace it. If the above
checks are not correct, the relay is defective and should be
replaced.
G.G.
G.G.
G.
Relay, DPST (double pole/single throw) is used onRelay, DPST (double pole/single throw) is used on
Relay, DPST (double pole/single throw) is used onRelay, DPST (double pole/single throw) is used on
Relay, DPST (double pole/single throw) is used on
model 39424.601.model 39424.601.
model 39424.601.model 39424.601.
model 39424.601.
It controls HIGH FAN and LOW FAN on Circuit 1 and 2. If
this relay is not wired correctly, Circuit 1 fan will not operate
with Circuit 1 compressor.
The relay has a 120 volt AC coil. To check the relay, first
verify all AC volts have been turned off to the unit.
Next remove the wires from terminals 2, 4, 6 and 8. Verify
the coil (terminals 0 and 1) are not energized (no AC
power). Continuity should not exist between terminals 2 to
4 or terminals 6 to 8. Next, energize the coil (terminals 0
and 1). Continuity should exist between terminals 2 to 4
and terminals 6 to 8. If the above checks are correct, the
relay is good DO NOT replace it. If the checks are not
correct, the relay is defective – replace it.
H.H.
H.H.
H.
Relay, DPST (double pole/single throw) is used onRelay, DPST (double pole/single throw) is used on
Relay, DPST (double pole/single throw) is used onRelay, DPST (double pole/single throw) is used on
Relay, DPST (double pole/single throw) is used on
Models 390XX.XXX. It controls the compressor.Models 390XX.XXX. It controls the compressor.
Models 390XX.XXX. It controls the compressor.Models 390XX.XXX. It controls the compressor.
Models 390XX.XXX. It controls the compressor.
The relay has a 24 volt AC coil. To check the relay, first
verify all AC volts have been turned off to the unit.
Next, remove the wires from terminals 2, 4, 6 and 8. Verify
the coil (terminals 0 and 1) are not energized (no AC
power). Continuity should not exist between terminals 2 to
4 or terminals 6 to 8. Next, energize the coil (terminals 0
and 1). Continuity should exist between terminals 2 to 4
and terminals 6 to 8. If the above checks are correct, the
relay is good – DO NOT replace it. If the checks are not
correct, the relay is defective – replace it.