Operation Manual

Programming Elite Control Operations Manual
12 L-2230 ENGLISH
Table 2: Programmable Parameters - Ranges and Factory Defaults
Parameter
Number Description
Factory
Default
Custom
Default Parameter Range
P-1 High Fan-Speed Limit 95 56 - 95
P-2 Low Fan-Speed Limit 50 30 - 75
P-3 Compressor Staging Time Delay 15 5 - 135 seconds
P-4 Temperature-Sensor Calibration Ambient temp Ambient plus or minus 10° F
P-5 Failsafe Level 3 0 = Minimal Protection
1 = Continuous No Display
2 = Continuous With Display
3 = Four Failures Reset Required
P-6
Low-Voltage Monitor
1
OFF OFF
95 = 95VAC for 115VAC Input Power
195 = 195VAC for 230VAC Input Power
P-7
De-Icing Cycle
2
1OFF
1 = On with 5°F Display Sensor Differential
2 = On with 7°F Display Sensor Differential
P-8 Pump Sentry OFF OFF
On = Select 100°F to 150°F
P-9 Display Brightness Control 15 4 (Dimmest) - 18 (Brightest)
P-10 Display Temperatures in Fahrenheit or
Celsius
F F = Fahrenheit Displayed
C = Celsius Displayed
P-11 Cycle Pump With Compressor or
Continuous Pump
CYC CYC = Cycle With Compressor
con = Continuous Pump
P-12 Reverse Fan Speeds During Heat Mode rEF nor = Normal Fan Operation
rEF = Reversed Fan in Heat Mode
P-13 Reverse-Cycle Heating or Electric-
Heat-Only Option Installed
nor nor = Reverse-Cycle Heating
ELE = Electric Heater Installed
P-14 Fan-Motor Type: Split Capacitor or
Shaded Pole
SC SC = Split Capacitor Fan Motor
SP = Shaded Pole Fan Motor
P-15 Reset Memorized Programming
Defaults
nor rST = Reset Defaults
nor = Normal
P-16 Reserved for future options
P-17 Reserved for future options
P-18 Air Filter Cleaning/Replacement Timer
Setting (x10 hours)
1
0 0 = Timer Disabled
10 - 250 (100 - 2500 hours)
P-19 Air Filter Cleaning/Replacement Value
(x10 hours) & Reset
1
0 Displays the elapsed time (in hours x10) since
the timer was started or reset. Press Down button
to reset value to 0, restart the timer, and clear the
display’s “FIL” reminder.
P-20
CAN-bus Unit ID
3
0 0 - 255 (Each control on a CAN-bus network
must have a unique Unit ID.)
P-21
CAN-bus Group ID
3
0 0 - 255 (Address for the control’s CAN-bus
network group. Should be different than any
CAN-bus Unit ID.)
P-22 Voltage Calibration AC Voltage Adjust to match the accurate voltage reading.
P-23
Set Point Temperature Differential
4
2 1 = 1°F (0.55°C) Differential
2 = 2°F (1.1°C) Differential
P-24
Moisture Mode Minimum Temperature
4
50°F 40-75°F (4.4-23.9°C)
1
This feature is only available in software revision A15 and newer.
2
This feature’s setting and behavior were modified in software revision A15 and newer. See description in text for details.
3
This feature is only available in sofware revision A16 and newer.
4
This feature is only available in software revision B23 and newer.