User manual
25
Deviations shall require the consent of the manufacturer.
If the cavity between the caravan wall and the refrigerator is sealed so that fumes
cannot penetrate the living area it is possible to vent the flue gas directly through the
upper grille without using the aluminium flue pipe. The waste gases escape to the
outside through the upper grill of the ventilation.
Do not use any kind of aluminium flue pipe (e.g. T-piece) to lead the flue gas out.
The flues of the oven escape to the outside through the roof ventilator.
Ventilation and extraction
8.4
A correct installation is important for correct operation of the appliance to ensure, there
is no build-up of heat at the back of the appliance. This heat must be allowed to esca-
pe into the open air.
In the event of high ambient temperatures, full performance of the cooling unit
can only be achieved by means of adequate ventilation and extraction.
The figures on the following pages show three possible installations of the RMT 7xxx
models. Ventilation of the refrigerator is ensured via two openings in the outer wall of
the vehicle (e.g. with Dometic ventilation grilles L 300). Special flue outlets, mounted on
the roof or the outer wall, are used for the oven's exhaust extraction and gas routing.
The model shown below depicts installation without flue with inner ventilation..
If ventilation and exhaust duct into the
vehicle is intended, fresh air supply
must not be obstructed. The room in
which the device is installed must have
one or several openings allowing fresh
air to enter (safety ventilation according
to EN 721). These openings must have
a total cross section of at least 100 cm².
There must be one or several ventilation
openings above the device with mini-
mum cross sections of 150 cm². These
have to be checked and if necessary
cleaned regularly. Roof and wall outlet
openings can be combined. Lower ven-
tilation openings must be no more than
100 mm above the inside floor. The ven-
tilation openings must by no means be
shut. Grilles and covers must be kept
clean and free of dust.
heat reflector
exhausts
L300
or
L500
8.4.1
Oven ventilation to vehicle's interior
(special equipment, model without flue)
Minimum ventilation height H
K
1400 - 1500 mm