Connecting the electrical power to the generator TEC29 EV AUS
24
9.3 Connecting 230 V
A
Guide the 230 V connection cable through the cable passage in the housing and
connect it to the 230 V terminals (fig. f 7, page 23).
Connect the earth cable to the earth connection on (fig. f 8, page 23).
9.4 Connecting the starter battery
A
Connect the positive terminal of the battery to the positive battery terminal
connection using a cable with a cross-section of 10 mm² for a length of < 6 m or
16 mm² for a length of > 6 m (fig. f 6, page 23).
Fit a 100 A fuse in the positive cable near the positive terminal of the starter
battery to protect the generator’s electrical system.
NOTICE!
Connect a relay or a change over switch to the vehicle’s electrical
system so that the generator is not damaged when the external
mains is connected (according to AS3001 regulation).
The neutral conductor is internally linked to the PE conductor. To
protect against automatic shutdown, make sure that a safety switch
(RCD switch, 30 mA) and an in all-pole overcurrent protection (e.g.
circuit breaker, 12 A) are installed (according to AS3001 regulation)
between the generator and the change over switch.
NOTICE!
The starter battery must have 12 V and a capacity of at least 60 Ah. Make
sure that the battery is fully charged.