Product Manual
EN
Connecting the electrical power to the generator TEC29 EV AUS
24
9.3 Connecting 230 V
A
➤ Guide the 230 V connection cable through the cable passage in the housing and
connect it to the 230 V terminals (fig. f 7, page 23).
➤ Connect the earth cable to the earth connection on (fig. f 8, page 23).
9.4 Connecting the starter battery
A
➤ Connect the positive terminal of the battery to the positive battery terminal
connection using a cable with a cross-section of 10 mm² for a length of < 6 m or
16 mm² for a length of > 6 m (fig. f 6, page 23).
➤ Fit a 100 A fuse in the positive cable near the positive terminal of the starter
battery to protect the generator’s electrical system.
NOTICE!
• Connect a relay or a change over switch to the vehicle’s electrical
system so that the generator is not damaged when the external
mains is connected (according to AS3001 regulation).
• The neutral conductor is internally linked to the PE conductor. To
protect against automatic shutdown, make sure that a safety switch
(RCD switch, 30 mA) and an in all-pole overcurrent protection (e.g.
circuit breaker, 12 A) are installed (according to AS3001 regulation)
between the generator and the change over switch.
NOTICE!
The starter battery must have 12 V and a capacity of at least 60 Ah. Make
sure that the battery is fully charged.