TEC29 EV AUS Connecting the electrical power to the generator
27
9.7 Connecting the float
Connect the float from the tank to the float connection (fig. f 9, page 23).
9.8 Connecting two genarators in parallel
I
When connecting the generators, note the following:
It is not possible to connect more than two generators in parallel.
To start one generator at a time the starter battery capacity has to be according
to the generator manual (minimum capacity: 60 Ah).
To start both generators at the same time you have to double the battery
capacity.
The cross section of the battery connection cable for each generator has to be at
least:
10 mm² if the total length is less than 6 m
16 mm² if the total length is more than 6 m
I
Proceed as follows (fig. i, page 28):
Connect each generator to a junction box (1; not included in the scope of
delivery).
The minimum cross section for each generator output cable is 2.5 mm².
Create a single output for the load (2) inside the junction box (1).
The minimum cross section for the parallel output cable is 6 mm².
Connect the battery‘s negative pole to ground.
Connect the output ground cable to ground.
To properly run the generators in parallel connect the inverters (4) of each
genarator using the parallel cable (3; available as accessory).
NOTE
Use only one starter battery to start both generators.
NOTE
The maximum distance between each generator to the junction box
is 15 m.
The maximum length difference between the output cables of the
generators must be 2 m.