Product Manual

EN
TEC29 EV AUS Operating the generator
33
GEN CAL
Message appears when the
generator is started up; it shows
the calibration phase which
takes place before each start-up.
The generator does not supply
any voltage.
The generator is running but
does not supply any voltage.
Wait a moment.
GEN WAIT
Message appears while you are
waiting for the generator to start
again.
The generator is switched off. Wait until the message has
disappeared then attempt
ignition again.
GEN ON
The generator is operating
normally.
Normal mode
–GEN ON
A second generator is in stand-
by and can be started.
=GEN ON
Two generators run in parallel.
GEN OFF
The generator is in stand-by and
can be started.
ENABLE AUTOSTART [HOLD]
CONFIRM
Message appears when the
automatic mode is switched on.
Controls are waiting for user
input
Press the start button within
15 seconds and hold down for
4seconds.
GEN AUTO
Automatic mode
The automatic mode is switched
on
PARALLEL ERROR
Parallel operation of two
generators
The generators don‘t run prop-
erly in parallel. Both generators
stop.
Check the parallel cable and
replace it, if necessary.
To reset the alarm switch each
generator off and on by pressing
the red on/off button.
COOLING
The generator keeps on running
but the inverter is off.
Wait until the unit cools down;
the generator will automatically
turn off.
Display message
Description
Generator behaviour Measures