1 General informations
1.12 Table describing the alarm messages appearing on the display
DISPLAYED MESSAGE DESCRIPTION GENERATOR BEHAVIOUR ACTIONS
LOW BATTERY
Indicates that the battery voltage is below the mini-
mum value necessary to start the generator.
The generator does not start.
Check the efficiency of the battery before starting
the generator.
OIL CHANGE
This message appears every time the hour counter
of the machine reaches the service interval pre-set to
change the engine oil.
The generator continues to run.
Change the oil (see p.20) before restarting the
generator by holding the start button down for
longer.
NO FUEL
Indicates that you are using the fuel reserve. The generator continues to run. Refuel.
OIL ALERT
There is no more oil in the oil tank. The generator stops. Fill up (see page 11).
GENERATOR ALERT!
General alarm message; it is displayed for instance
when the check ring of the carburettor throttle (step
motor) is defective and the M110 module cannot che-
ck the motor speed
The generator stops.
SeeTroubleshooting table on page 18. If the
problem persists, address to the nearest service
centre.
OVERLOAD!
Indicates an output overload of the supplied sy-
stems.
The inverter stops and voltage is no longer
supplied, but the engine continues to run for a
correct cooling of the internal parts.
Reduce the connected load, wait a few minutes
to cool down the generator. Stop the engine by
pressing the main switch button. Then restart
the generator.
SHORT CIRCUIT
Indicates an output short of the supplied systems.
The inverter stops and voltage is no longer
supplied, but the engine continues to run for a
correct cooling of the internal parts.
Check all the connected systems, wait a few
minutes to cool down the generator. Stop the
engine by pressing the main switch button.
OVER TEMPERATURE
This message is displayed in the event of a thermal
overload.
The inverter stops and voltage is no longer sup-
plied. The engine continues to run for a correct
cooling of the internal parts, then stops and the
message displayed is “RESTART GEN?”.
Let the generator cool down, wait a few minutes
and restart the unit.
LOW POWER ENGINE
Signals a reduction of the voltage supplied to the
inverter.
The generator stops.
Reduce the connected load and restart the
generator.
RESTART GEN?
This message appears after any stop of the ge-
nerator.
The generator stops. Turn off and restart the generator.
GEN CAL
This message appears at the generator start-up and
indicates the calibration phase preceding any start-
up. The generator does not produce current yet.
The generator run but voltage is not supplied. Wait a few seconds.
GEN WAIT
Message displayed between one start attempt and
the other.
The generator not run.
Wait until the message goes off before attemp-
ting a new start.
GEN ON
Indicates that the generator is running.
GEN OFF
Indicates that the generator not run or is ready to
start
The generator not run.
Push the start button if you want to restart the
generator